Plan Review Notes For Permit 15090082 |
Permit Number |
15090082 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-09-30 10:20:39 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. PAPA VALUE FOR THIS UNIT IS $94, 683 AND PROPOSED | | IMPROVEMENT IS $28,674 WHICH EXCEEDS 30% OF THE | | ASSESSED VALUE. FBC 5TH EDITION ENERGY CONSERVATION, | | C101.4.3, C202, THIS IS A "RENOVATED BUILDING". | | C101.4.7, PROVIDE THE FENESTRATION DATA FROM THE | | MANUFACTURER WHICH SHOWS COMPLIANCE WITH C402.1.1. | | | | 2. REVISE PLAN TO INCLUDE THE BUILDING HEIGHT, FBC | | 1609. | | | | 3. ACCESSIBLE ROUTE IS NOT CLEAR. PROVIDE THRESHOLD | | DETAIL FOR PROPOSED DOORS, FBC 5TH ED. ACCESSIBILITY | | 404.2.5. | | | | 4. A SEPARATE APPLICATION HAS BEEN SUBMITTED TO | | RENOVATE THREE UNITS. CLARIFY; ARE THE THREE UNITS | | INCLUDED IN THIS APPLICATION? IF THREE UNITS ARE | | INCLUDED IN THIS SCOPE, THREE SEPARATE PERMITS REQUIRED | | AND ITEM 1 WOULD NEED TO BE RE-EVALUATED. | | | | IF APPLICANT INTENTION IS TO COMBINE THE UNITS, A UNITY | | OF TITLE THROUGH THE ENGINEERING DEPARTMENT IS | | REQUIRED. | | | | HTTP://WPB.ORG/WP-CONTENT/UPLOADS/SITES/7/2012/05/2011- | | 11-14-16-09-54-APPLICATIONFORUNITYOFTITLE.PDF | | | | IF THE THREE UNITS HAVE ALREADY BEEN COMBINED THROUGH A | | UNITY OF TITLE, PROVIDE THE UNITY OF TITLE BOOK/PAGE | | RECORDING NUMBER AND ADVISE AS TO CORRECT VALUE. | | | | | | | | | | | | |
|