Plan Review Notes
Plan Review Notes For Permit 15090079
Permit Number 15090079
Review Stop E
Sequence Number 4
Notes
Date Text
2015-11-09 16:57:09ALMOST ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED. THOSE THAT HAVE NOT HAVE BEEN
 MENTIONED TO THE DESIGN PROFESSIONAL TO AVOID SURPRISES
 IN THE FIELD. THEY ARE:
 INCORRECT CODE MENTIONED ON THE PLANS. THIS WORK SHALL
 COMPLY WITH THE 2011 EDITION OF THE NEC.
 MANDATORY SWITCHING REQUIREMENTS OF THE FBC-E SHALL BE
 COMPLIED WITH
 RECESSED LIGHTING SHALL BE SEALED TO LIMIT THE TRANSFER
 OF AIR BETWEEN CONDITIONED AND NON CONDITIONED SPACE.