Plan Review Notes
Plan Review Notes For Permit 15090079
Permit Number 15090079
Review Stop E
Sequence Number 2
Notes
Date Text
2015-11-03 15:10:55THOUGH THESE DRAWINGS WERE ONCE BEFORE REVIEWED. THE
 FAILURE TO PROVIDE A NARRATIVE PROMPTED ME TO CONDUCT A
 COMPLETE REVIEW OF THE PLANS FOR A SECOND TIME.
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE
 2011 EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE);
 THE 5TH EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS
 APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED.
  
 1. THE CODE ANALYSIS BOX IS REFERENCING STANDARDS FROM
 THE 2010 FBC, NO LONGER IN EFFECT. THE APPLICABLE CODE
 TO WHICH YOU SHALL CONFORM IS AS MENTIONED ABOVE.
 2. I NOTICE THAT THE FIXTURE SCHEDULE INDICATES THE USE
 OF RECESSED LUMINARIES WITHOUT MENTIONING THE
 REQUIREMENTS OF FBC-ENERGY CONSERVATION SECTION
 402.4.8, WHICH REQUIRES THAT ALL RECESSED LIGHTING BE
 IC RATED AND SEALED TO PREVENT AIR LEAKAGE FROM THE
 CONDITIONED AIR SPACE INTO THE NON-CONDITIONED AIR
 SPACE.
 3. YOU SHALL SUBMIT LIGHT DENSITY ALLOWANCE
 CALCULATIONS AS INDICATED IN FBC-E SECTIONS 405.5.
 4. NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN
 OUTLET AT EVERY PEDESTRIAN ENTRY, FOR EVERY COMMERCIAL
 OCCUPANCY.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  