2015-11-03 15:10:55 | THOUGH THESE DRAWINGS WERE ONCE BEFORE REVIEWED. THE |
| FAILURE TO PROVIDE A NARRATIVE PROMPTED ME TO CONDUCT A |
| COMPLETE REVIEW OF THE PLANS FOR A SECOND TIME. |
| THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE |
| 2011 EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE); |
| THE 5TH EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS |
| APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED. |
| |
| 1. THE CODE ANALYSIS BOX IS REFERENCING STANDARDS FROM |
| THE 2010 FBC, NO LONGER IN EFFECT. THE APPLICABLE CODE |
| TO WHICH YOU SHALL CONFORM IS AS MENTIONED ABOVE. |
| 2. I NOTICE THAT THE FIXTURE SCHEDULE INDICATES THE USE |
| OF RECESSED LUMINARIES WITHOUT MENTIONING THE |
| REQUIREMENTS OF FBC-ENERGY CONSERVATION SECTION |
| 402.4.8, WHICH REQUIRES THAT ALL RECESSED LIGHTING BE |
| IC RATED AND SEALED TO PREVENT AIR LEAKAGE FROM THE |
| CONDITIONED AIR SPACE INTO THE NON-CONDITIONED AIR |
| SPACE. |
| 3. YOU SHALL SUBMIT LIGHT DENSITY ALLOWANCE |
| CALCULATIONS AS INDICATED IN FBC-E SECTIONS 405.5. |
| 4. NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN |
| OUTLET AT EVERY PEDESTRIAN ENTRY, FOR EVERY COMMERCIAL |
| OCCUPANCY. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| |