2015-09-09 14:10:301ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1.THE WIDTH OF THE BATHROOM DOES NOT ALLOW FOR 60IN.
 CLEARANCE AT TOILET.
 PER FBC ACC. 2014 SEC.604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL. HTTP://FLORIDABUILDIN
 G2.ICCSAFE.ORG/APP/BOOK/CONTENT/2014_FLORIDA/ACCESSIBIL
 ITY%20CODE/IMAGES/FAC_RK_BITMAP%2079.JPG
 2. FBC ACC. SEC 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE.IF MEASURED 36IN TO CENTER THE BAR
 WILL BE TO HIGH.
 3.SHALL SHOW HEIGHT OF TOILET.
 FBC ACC. SEC 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
 4.PLANS MUST BE SIGNED AND SEALED.
 PER. FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN