Date |
Text |
2015-09-09 14:10:30 | 1ST REVIEW: FBC 2014 |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| 561-805-6711 |
| [email protected] |
| |
| |
| PLUMBING COMMENTS: |
| |
| 1.THE WIDTH OF THE BATHROOM DOES NOT ALLOW FOR 60IN. |
| CLEARANCE AT TOILET. |
| PER FBC ACC. 2014 SEC.604.3.1 SIZE. |
| CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| PERPENDICULAR FROM THE REAR WALL. HTTP://FLORIDABUILDIN |
| G2.ICCSAFE.ORG/APP/BOOK/CONTENT/2014_FLORIDA/ACCESSIBIL |
| ITY%20CODE/IMAGES/FAC_RK_BITMAP%2079.JPG |
| 2. FBC ACC. SEC 609.4 POSITION OF GRAB BARS. |
| GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) |
| MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| THE GRIPPING SURFACE.IF MEASURED 36IN TO CENTER THE BAR |
| WILL BE TO HIGH. |
| 3.SHALL SHOW HEIGHT OF TOILET. |
| FBC ACC. SEC 604.4 SEATS. |
| THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES |
| (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS |
| SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION. |
| 4.PLANS MUST BE SIGNED AND SEALED. |
| PER. FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN |