Plan Review Notes For Permit 15081172 |
Permit Number |
15081172 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-09-08 11:34:39 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. FOR BEDROOM WINDOWS, REVISE PLAN TO EXISTING | | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR | | BEDROOMS, FBC R310, FBC EB 704.1. THE CLEAR OPENING | | CANNOT BE REDUCED BY MORE THAN 5%. | | | | TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION | | NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN | | HEIGHT: | | | | STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS | | - AWNING, CASEMENT, SINGLE HUNG? | | | | STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE. | | CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE | | WINDOW IS FULLY OPEN. | | | | STATE WHAT THE PROPOSED CLEAR OPENING DIMENSIONS ARE. | | THIS CAN BE OBTAINED FROM THE MANUFACTURER. | | | | DIMENSIONS PROVIDED ARE THE DIMENSIONS WHEN BOTH PANELS | | ARE REMOVED FROM THE WINDOW. EITHER EXPLAIN HOW THIS | | CAN BE DONE FROM THE OUTSIDE (RESCUE OPENING) OR REVISE | | TO INCLUDE CLEAR OPENING DIMENSIONS (WINDOW IN OPEN | | POSITION BUT NOT REMOVED FROM FRAME). | | | | | | |
|