Plan Review Notes
Plan Review Notes For Permit 15081167
Permit Number 15081167
Review Stop P
Sequence Number 1
Notes
Date Text
2015-09-02 05:04:311) POOL SPECS BOX: THE TURNOVER RATE FOR THE POOL IS
 NOTED AS 6 HR. ? MIN. FOR 21,542 GALS. I HAVE
 CALCULATED A TURNOVER RATE OF 11.58 HOURS. CLARIFY.
 2) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS
 FOR THE HEAT PUMP. THE INFORMATION SHALL CLEARLY SHOW
 COMPLIANCE WITH THE 2014 FL. ENERGY CODE SEC.R403.9.1 &
 R403.9.1.2. HEAT PUMPS SHALL HAVE A MINIMUM COP OF 4.0
 AND SHALL BE TESTED IN ACCORDANCE WITH AHRI 1160, TABLE
 2.A TEST REPORT FROM AN INDEPENDENT LABORATORY IS
 REQUIRED TO VERIFY PROCEDURE COMPLIANCE.
 3) 2014 FBC- ENERGY CODE SEC. R 403.9.2 - TIME SWITCHES
 OR OTHER CONTROL METHODS THAT CAN AUTOMATICALLY TURN
 OFF AND ON HEATERS AND PUMPS ACCORDING TO A PRESET
 SCHEDULE SHALL BE INSTALLED ON ALL HEATERS AND PUMPS.
 HEATERS, PUMPS AND MOTORS THAT HAVE BUILT IN TIMERS
 SHALL BE DEEMED IN COMPLIANCE WITH THIS REQUIREMENT.
 4) SUBMIT A COPY OF THE PUMP CURVE FOR THE POOL/SPA
 PUMP AND IDENTIFY THE TOTAL DYNAMIC HEAD CALCULATIONS
 PER FOR THIS POOL PER ANSI/APSP-7 SEC. 4.4.1.
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR BOTH
 CHANNEL DRAINS TO ENSURE COMPLIANCE WITH ANSI/APSP-7
 SEC.5.5.1
  
  
  
 PLUMBING PLAN REVIEW