2016-02-12 12:45:493RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15081154: MODEL A- #1200.
 2/12/16
  
 1) THERE ARE SEVERAL CONFLICTS BETWEEN THE AC COOLING
 LOAD CALCULATIONS, THE ENERGY CALCULATIONS AND THE AC
 PLANS.
 A) THE AC CALCULATIONS INDICATE A 4-TON LOAD FOR AC
 A-01 WHICH IS CONDITIONING THE 1ST LEVEL, HOWEVER SHEET
 M401 INDICATES A 3-TON SYSTEM FOR THE 1ST LEVEL SYSTEM.
 PLEASE NOTE THAT THE SYSTEM IS MISLABED AC-B, AND REFER
 TO SECTION R403.6.1.1FBC-14 ENERGY CONSERVATION WHICH
 REQUIRES SYSTEMS TO BE SIZED NOT LESS NOT THAN THE
 CALCULATED LOADS.
 B) AC CALCULATIONS HAVE BEEN SUBMITTED FOR ACA- 02
 HOWEVER THE PLANS ARE INDICATING ACB-02.
 C) AC CALCULATIONS HAVE BEEN SUBMITTED FOR VAV A-01B,
 HOWEVER THAT SYSTEM IS NOT SHOWN ON THE PLANS.
 D) THE SUBMITTED ENERGY CALCULATION FORM R405-2014
 SHOWS COMPLIANCE DATA FOR A SINGLE COOLING SYSTEM WHICH
 APPEARS TO ACTUALLY BE COMPLIANCE DATA FOR THE TWO
 4-TON SYSTEMS SHOWN IN THE SCHEDULE COMBINED AND
 AVERAGED. PLEASE PROVIDE COMPLIANCE DATA FOR EACH
 INDIVIDUAL SYSTEM AND COMPARE WITH THE PLANS WHICH
 INDICATES A 3-TON AND A 4-TON SYSTEM.
 E) THE AC CALCULATIONS ARE INDICATING THE FRONT DOOR
 FACES EAST HOWEVER THE FRONT DOOR IS FACING NORTH.
  