Plan Review Notes For Permit 15081154 |
Permit Number |
15081154 |
|
Review Stop |
G |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2016-02-06 03:52:35 | 1) SHT. M401 - DRYER COMBUSTION AIR CALCS. - THE TABLE | | SHOW THE LAUNDRY ROOM VOLUME AS 1750 CUBIC FEET. PLEASE | | EXPLAIN HOW A CLOSET THAT MEASURES 3 FT. BY 7 FT. BY | | APPROX. 8 FT.HIGH EQUALS 1750 CUBIC FEET. | | 2) SUBMIT A GAS RISER FOR THE "A" TYPE UNIT.FBC SEC. | | 107.2.1. | | 3) THE REQUIREMENTS FOR COMBUSTION AIR FOR THE DRYER | | HAVE BEEN ADDRESSED IN TWO DIFFERENT WAYS; ONE WITH 50 | | CU. FT. FOR EACH 1000 BTU'S AND ALSO WITH WOOD LOUVER | | DOORS. WHICH METHOD IS BEING USED? IF WOOD LOUVER DOORS | | ARE GOING TO BE USED, SHOW THE DIMENSIONS (LXW) OF THE | | LOUVERED AREA OF EACH DOOR. 25% OF THIS AREA IS THE NET | | FREE AREA OF THE LOUVERS THAT IS TO BE USED IN | | CALCULATING THE REQUIRED SQUARE INCH AREA FOR | | COMBUSTION AIR.2014 FGC SEC.304.10, 304.5.3.1.ALSO, | | REFER TO YOUR RESPONSE TO MECHANICAL REVIEW COMMENT | | #25. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|