Plan Review Notes
Plan Review Notes For Permit 15081154
Permit Number 15081154
Review Stop E
Sequence Number 3
Notes
Date Text
2016-02-18 09:15:32WHILE STAMPING THE SECOND SET OF PLANS, A DISCREPANCY
 WAS NOTICED THAT MUST BE CORRECTED BEFORE PROCEEDING.
 BOTH SETS OF ELECTRICAL PLANS DO NOT MATCH. ACCORDING
 TO THE SHEET INDEX ON THE COVER OF BLDG A SET. PAGES
 E301 & E302 ARE THE POWER & LIGHTING FLOOR PLANS FOR
 THE A UNITS AND E401 & 402 ARE THE SAME FOR THE B
 UNITS. WELL ONE SET HAS THE 301 & 302 SHEETS WHILE THE
 OTHER HAS THE 401 & 402 SHEETS.
  
2016-02-17 14:31:50WITH THE EXCEPTION OF THE RECORDED EASEMENT, ALL
 PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED.THEREFORE THIS PERMIT HAS BEEN
 CONDITIONALLY ISSUED PROVIDED A COPY OF THE RECORDED
 EASEMENT IS AVAILABLE FOR INSPECTION AT THE TIME OF
 FINAL ELECTRICAL INSPECTION.
  