2015-12-01 14:28:13 | 2ND REVIEW: FBC 2014 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | | | GAS COMMENTS: | | | | 1.MEP SHEETS DO NOT COMPLY WITH FL ADMEN CODE SEC | | 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND | | SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | DOCUMENTS. | | ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN | | ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025, | | F.S., AND RULE 61G15-23.001, F.A.C. MAY BE PHYSICALLY | | SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE | | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE | | USED. | | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY | | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY | | OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE | | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL | | NOT RENDER THE SIGNATURE ILLEGIBLE. | | | | 2.PLEASE PROVIDE DETAIL AND MANUFACTURE INSTALLATION | | GUIDE FOR WATER HEATER VENT. PER WPB AMEND TO FBC SEC | | 107.2.1 SHEET M401 IS REFERENCED IN YOUR RESPONSE BUT | | IT IS NOT INCLUDED IN THE PLAN SET. | | |
|