2015-12-29 17:13:58 | RESIDENTIAL (R3) RE-ROOF THIRD BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 1- NEW CLAY TILE FLORIDA PRODUCT APPROVAL FL17152-R1 |
| WAS SUBMITTED. LIMITATION #3 ON THIS PRODUCT APPROVAL |
| SPECIFIES THAT TILES SHALL BE MECHANICALLY ATTACHED FOR |
| WIND LOAD RESISTANCE. PRODUCT APPROVAL SUBMITTED |
| DOESN'T SPECIFY THE TILE ATTACHMENT RESISTANCE. NEED |
| THIS INFORMATION TO VERIFY COMPLIANCE WITH THE DESIGN |
| PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION |
| (2014). PROVIDE COMPLETE CALCULATIONS SHOWING HOW THE |
| PROPOSED MECHANICAL ATTACHMENT IS GOING TO MEET THE |
| DESIGN PRESSURES OF SEC. R301. |
| NOTE: NOA 14-0107.02 PREVIOUSLY SUBMITTED HAD ALL THIS |
| INFORMATION. THE ONLY THING THAT WAS MISSING WAS THE |
| PRODUCT APPROVAL FOR THE ADHESIVE TO BE USED. |
| |
| 2- FLAT ROOF FLORIDA PRODUCT APPROVAL FL5680-R15 |
| SUBMITTED: CLEARLY MARK WHICH APPROVED ASSEMBLY IS |
| GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| DESIGN PRESSURES OF SEC. R301. THIS BUILDING IS LOCATED |
| IN EXPOSURE "C". IF THE SELECTED ASSEMBLY DOESN'T MEET |
| THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED |
| AND SEALED RAS 117 CALCULATIONS WOULD BE REQUIRED. SEE |
| NOTE #8 ON PAGE 2 OF 76. |
| (REPEAT COMMENT. NOT ADDRESSED AT ALL. THIRD TIME). |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |