2015-10-16 18:14:10 | RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 1- ORIGINALLY THIS HOUSE WAS DESIGNED TO HAVE SHINGLES |
| ROOFING. PROPOSAL TO INSTALL CLAY TILES REQUIRES |
| ENGINEERING ANALYSIS TO VERIFY IF THE STRUCTURE IS |
| ADEQUATE TO RECEIVE THE ADDITIONAL LOAD. SEC. 107.2.1.3 |
| CITY AMENDMENTS. |
| |
| RESPONSE: |
| ENGINEER LETTER SUBMITTED: |
| (1) IT APPEARS THAT WRONG HOUSE WAS INSPECTED BY THE |
| ENGINEER. IT LOOKS LIKE THE ENGINEER INSPECTED THE |
| HOUSE LOCATED AT 505 38TH STREET AS STATED ON THE |
| LETTER. THE HOUSE FOR THIS PERMIT IS 502 38TH STREET, |
| WHICH IS LOCATED ACROSS THE STREET. THE BUILDING |
| FRAMING SYSTEM IS DIFFERENT FOR BOTH HOUSES. ONE HOUSE |
| WAS BUILT IN 1954 AND THE OTHER ONE WAS BUILT IN 1925. |
| THERE MAY NOT BE A TRUSS SYSTEM ON THE HOUSE BUILT IN |
| THE 1925'S. ENGINEER TO REVISE ADDRESS AND PROVIDE |
| COMPLETE ROOF FRAMING AND SUPPORTING WALLS INFORMATION |
| FOR THE CORRECT HOUSE. SEC. 107.2.1.3 CITY AMENDMENTS. |
| |
| (2) THE ORIGINAL ROOF COVERING OF THIS HOUSE WAS |
| SHINGLES NOT CLAY TILES. REVISE AS REQUIRED. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| (3) ENGINEER TO PROVIDE ALL HIS INFORMATION AND THE |
| FIRM CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED BY |
| SEC. 61G15-23.002 AND CHAPTER 471 FLORIDA STATUTE. |
| |
| 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR THE TILE ADHESIVE LISTED ON THE |
| CLAY TILE NOA. |
| (REPEAT COMMENT. NOT ADDRESSED AT ALL). |
| |
| 3- FLAT ROOF FLORIDA PRODUCT APPROVAL FL5680-R15 |
| SUBMITTED: CLEARLY MARK WHICH APPROVED ASSEMBLY IS |
| GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| DESIGN PRESSURES OF SEC. R301. THIS BUILDING IS LOCATED |
| IN EXPOSURE "C". IF THE SELECTED ASSEMBLY DOESN'T MEET |
| THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED |
| AND SEALED RAS 117 CALCULATIONS WOULD BE REQUIRED. SEE |
| NOTE #8 ON PAGE 2 OF 76. |
| (REPEAT COMMENT. NOT ADDRESSED AT ALL). |
| |