Plan Review Notes For Permit 15081110 |
Permit Number |
15081110 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2015-12-11 09:04:06 | SHELL SPACE SIGNAGE INDICATING "NO STORAGE" AND ADDING | | A 40-MINUTE WALL FIRE RATING IS A GOOD SOLUTION FOR THE | | TEMPORARY SHELL SPACE INCIDENTAL STORAGE. IF THE SHELL | | SPACE BECOMES PERMANENT STORAGE EXCEEDING THE | | INCIDENTAL THRESHOLD (10%) OR BECOMES A PERMANENT | | OCCUPANCY OTHER THAN ASSEMBLY, THE FIRE RATING ON THE | | WALLS WILL HAVE TO BE RE-EVALUATED FOR CODE COMPLIANCE. |
|