Plan Review Notes
Plan Review Notes For Permit 15081110
Permit Number 15081110
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2015-12-11 09:04:06SHELL SPACE SIGNAGE INDICATING "NO STORAGE" AND ADDING
 A 40-MINUTE WALL FIRE RATING IS A GOOD SOLUTION FOR THE
 TEMPORARY SHELL SPACE INCIDENTAL STORAGE. IF THE SHELL
 SPACE BECOMES PERMANENT STORAGE EXCEEDING THE
 INCIDENTAL THRESHOLD (10%) OR BECOMES A PERMANENT
 OCCUPANCY OTHER THAN ASSEMBLY, THE FIRE RATING ON THE
 WALLS WILL HAVE TO BE RE-EVALUATED FOR CODE COMPLIANCE.