2015-11-04 10:38:33 | 2ND REVIEW: FBC 2014 MECHANICAL | | PERMIT #15081110 | | MASTER #14030096 | | | | 1) THE RESPONSE NARRATIVE TO COMMENT #2 FROM THE 1ST | | REVIEW INDICATES THAT THE SECOND FLOOR ATRIUM WALL THAT | | THE DUCT IS PENETRATED IS NOT A FIRE-RATED WALL, AND | | THEREFORE NO DAMPER IS REQUIRED. PLEASE REFER TO | | SECTION 404.6 FBC-10 AND INDICATE WHICH OF THE THREE | | EXCEPTIONS LISTED IS BEING USED TO DE-RATE THE WALL. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] |
|