2015-11-19 15:10:12WE CANNOT BASE OUR INSPECTIONS/PLAN REVIEWS ON FUTURE
 DESIGNS AND RISK THE CONSTRUCTION BEING LEFT UNFINISHED
 AND NON-CODE COMPLIANT. A FLOOR-TO-FLOOR FIRE
 SEPARATION IS REQUIRED BY CODE OR THE DESIGN NEEDS TO
 WHOLLY COMPLY AS EITHER A COMMUNICATING SPACE, AN
 ATRIUM, A MEZZANINE OR A CONVENIENCE OPENING. THE
 CURRENT FIELD CONDITIONS DO NOT FULLY COMPLY WITH ANY
 OF THESE OPTION. HENCE, A FINAL FIRE INSPECTION WILL
 NOT PASS INSPECTION AND A CERTIFICATE OF OCCUPANCY WILL
 NOT BE ISSUED UNTIL THE 2ND FLOOR AMENITIES AREA DESIGN
 AND CONSTRUCTION HAS BEEN COMPLETED. THIS ISSUE
 GENERATED THE FOLLOWING COMMENTS DURING FIRE PLAN
 REVIEW OVER A YEAR AGO (09/30/14):
  
 705 NORTH OLIVE AVENUE
 PERMIT #14030096
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - THE AMENITIES/LEASING OFFICE IS NOT
 APPROVED FOR CONSTRUCTION AT THIS TIME UNTIL THE
 FLOOR/CEILING OPENINGS DESIGN HAS BEEN RESOLVED*****
  
 ROUND #3 COMMENTS:
 REPEAT COMMENT - SHEET A-0.1.2: SEVERAL AREAS IN THE
 AMENITIES/LEASING OFFICE ARE OPEN TO THE FLOOR BELOW.
 THE DESIGN SHALL CONFORM TO SECTION 8.6 VERTICAL
 OPENINGS AS EITHER A COMMUNICATING SPACE, CONVENIENCE
 OPENING, ATRIUM, OR MEZZANINE. FOR INSTANCE, EACH
 OCCUPANT NOT IN THE COMMUNICATING SPACE (SUCH AS
 AMENITY SECOND FLOOR REST ROOM) NEEDS TO HAVE ACCESS TO
 AT LEAST ONE EXIT WITHOUT HAVING TO ENTER THE
 COMMUNICATING SPACE, OR AS A CONVENIENCE OPENING, THE
 OPENINGS NEED TO BE SEPARATED FROM CORRIDORS.
  
 WESLEY R. JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR/INSPECTOR
 BUREAU OF FIRE PREVENTION
 WEST PALM BEACH FIRE RESCUE
 FIRE STATION #1: 561.804.4752
 CONST. SERVICES : 561.805.6730
 [email protected]
  
  
 THE SECOND FLOOR AMENITIES AREA IS NO LONGER FIRE
 SEPARATED FROM THE FIRST FLOOR AS IS REQUIRED FOR
 FLOOR-TO-FLOOR SEPARATION. OTHERWISE, AS PREVIOUSLY
 INDICATED IN 2014: SHEET A-0.1.2: SEVERAL AREAS IN THE
 AMENITIES/LEASING OFFICE ARE OPEN TO THE FLOOR BELOW.
 THE DESIGN SHALL CONFORM TO SECTION 8.6 VERTICAL
 OPENINGS AS EITHER A COMMUNICATING SPACE, CONVENIENCE
 OPENING, ATRIUM, OR MEZZANINE. FOR INSTANCE, EACH
 OCCUPANT NOT IN THE COMMUNICATING SPACE (SUCH AS
 AMENITY SECOND FLOOR REST ROOM) NEEDS TO HAVE ACCESS TO
 AT LEAST ONE EXIT WITHOUT HAVING TO ENTER THE
 COMMUNICATING SPACE, OR AS A CONVENIENCE OPENING, THE
 OPENINGS NEED TO BE SEPARATED FROM CORRIDORS.