Notes
Date Text
2015-11-21 14:10:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. A0.1.2, FIRE RESISTANCE RATINGS HAVE BEEN REMOVED
 FROM THE SECOND FLOOR AMENITY AREA. IT IS NOT CLEAR HOW
 THIS AREA COMPLIES WITH FBC CHAPTER 7. REVISE PLAN TO
 INCORPORATE THE CODE WHICH SHOWS COMPLIANCE FOR THE NON
 RATED OPENINGS BETWEEN THE FIRST FLOOR AND SECOND
 FLOOR, FBC 712.4, 404.
  
 SEE ALSO FIRE COMMENTS AND PROVISO.
  
 2. A0.1.2, REVISE PLAN TO INCLUDE SQUARE FOOT PER
 OCCUPANT
  
 3. A0.1.2, DOOR FROM ASSEMBLY AREA TO ELEVATOR LOBBY IS
 TO SWING IN DIRECTION OF EGRESS TRAVEL, FBC1008.1.2.
  
 4. 2ND FLOOR AMENITY AREA, FIRE DAMPER WAS REMOVED, BUT
 IT APPEARS THAT BOTH THE WALL AND FLOOR ARE REQUIRED TO
 BE RATED, 713.1.
  
 5. A2.1.2, GRIDLINE G.A G.1, IT APPEARS THAT A PORTION
 OF THE FUTURE ADDITION WAS INCLUDED; PLEASE REMOVE AS
 IT IS NOT COVERED UNDER THE SCOPE OF THIS PERMIT.
  
 6. S1.4.5A, SPECIFY FLOOR LIVE LOAD FOR 2ND FLOOR
 AMENITY AREA, FBC TABLE 1607.
  
 7. BUILDING FLOOR HEIGHTS WERE REMOVED FROM S1.6A,
 S1.5A, AND POSSIBLY OTHER PAGES. INCLUDE ON THE PLAN,
 FBC107.
  
  
  