Plan Review Notes For Permit 15081110 |
Permit Number |
15081110 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-11-21 14:10:19 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. A0.1.2, FIRE RESISTANCE RATINGS HAVE BEEN REMOVED | | FROM THE SECOND FLOOR AMENITY AREA. IT IS NOT CLEAR HOW | | THIS AREA COMPLIES WITH FBC CHAPTER 7. REVISE PLAN TO | | INCORPORATE THE CODE WHICH SHOWS COMPLIANCE FOR THE NON | | RATED OPENINGS BETWEEN THE FIRST FLOOR AND SECOND | | FLOOR, FBC 712.4, 404. | | | | SEE ALSO FIRE COMMENTS AND PROVISO. | | | | 2. A0.1.2, REVISE PLAN TO INCLUDE SQUARE FOOT PER | | OCCUPANT | | | | 3. A0.1.2, DOOR FROM ASSEMBLY AREA TO ELEVATOR LOBBY IS | | TO SWING IN DIRECTION OF EGRESS TRAVEL, FBC1008.1.2. | | | | 4. 2ND FLOOR AMENITY AREA, FIRE DAMPER WAS REMOVED, BUT | | IT APPEARS THAT BOTH THE WALL AND FLOOR ARE REQUIRED TO | | BE RATED, 713.1. | | | | 5. A2.1.2, GRIDLINE G.A G.1, IT APPEARS THAT A PORTION | | OF THE FUTURE ADDITION WAS INCLUDED; PLEASE REMOVE AS | | IT IS NOT COVERED UNDER THE SCOPE OF THIS PERMIT. | | | | 6. S1.4.5A, SPECIFY FLOOR LIVE LOAD FOR 2ND FLOOR | | AMENITY AREA, FBC TABLE 1607. | | | | 7. BUILDING FLOOR HEIGHTS WERE REMOVED FROM S1.6A, | | S1.5A, AND POSSIBLY OTHER PAGES. INCLUDE ON THE PLAN, | | FBC107. | | | | | | |
|