Plan Review Notes For Permit 15081110 |
Permit Number |
15081110 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-09-18 13:37:11 | THE SECOND FLOOR AMENITIES AREA IS NO LONGER FIRE | | SEPARATED FROM THE FIRST FLOOR AS IS REQUIRED FOR | | FLOOR-TO-FLOOR SEPARATION. OTHERWISE, AS PREVIOUSLY | | INDICATED IN 2014: SHEET A-0.1.2: SEVERAL AREAS IN THE | | AMENITIES/LEASING OFFICE ARE OPEN TO THE FLOOR BELOW. | | THE DESIGN SHALL CONFORM TO SECTION 8.6 VERTICAL | | OPENINGS AS EITHER A COMMUNICATING SPACE, CONVENIENCE | | OPENING, ATRIUM, OR MEZZANINE. FOR INSTANCE, EACH | | OCCUPANT NOT IN THE COMMUNICATING SPACE (SUCH AS | | AMENITY SECOND FLOOR REST ROOM) NEEDS TO HAVE ACCESS TO | | AT LEAST ONE EXIT WITHOUT HAVING TO ENTER THE | | COMMUNICATING SPACE, OR AS A CONVENIENCE OPENING, THE | | OPENINGS NEED TO BE SEPARATED FROM CORRIDORS. | | | | |
|