2015-09-15 14:10:40 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. ENGINEERING PREPARED BY RICHARDSON ENGINEERING HAS A |
| PROJECT ADDRESS IN LAKE WORTH. REVISE, FBC 107. |
| |
| 2. INCORRECT CODE REFERENCE; GOVERNING CODE CHANGED ON |
| JUNE 31, 2015. |
| |
| 3. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS |
| FS471 (SOILS REPORT). |
| |
| 4. INCLUDE PROJECT INFORMATION ON ENGINEERING - |
| ADDRESS, SF AREA OF PROPOSED STRUCTURE, NUMBER OF |
| STORIES, HEIGHT, FBC 107. |
| |
| 5. REVISE STRUCTURAL DETAILS SO THEY ARE COMPLETE. ALL |
| FASTENERS, SIZES, MATERIALS SHOULD BE SPECIFIED. FOR |
| INSTANCE: |
| |
| SECTION 1 SPECIFIES "HOLE FOR STRAPS"; PROVIDE A |
| DETAIL. |
| FOUNDATION PLAN SHOWS TRIPLE AND DOUBLE 2X8 BEAMS BUT |
| DOES NOT SPECIFY MATERIAL OR HOW THESE BEAMS WILL BE |
| CONSTRUCTED (FASTENED TOGETHER). |
| PLAN HAS NO INFORMATION REGARDING THE STRUCTURE TO BE |
| RELOCATED OTHER THAN A REFERENCE TO "MOVED HOUSE." |
| SECTIONS 2 AND 3 SHOW 3" COVER, BUT FOOTER STEEL NOT |
| SHOWN OR SPECIFIED. |
| SECTION 1, FOOTING STEEL SHOWN BUT NOT SPECIFIED. |
| |
| 6. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED. |
| CONTACT 561-233-5025 FOR MORE INFORMATION. |
| |
| 7. ADVISORY ONLY, THIS PERMIT WILL BE ISSUED AT |
| CONTRACTOR'S RISK, SEE FBC 105.13 (PHASED |
| CONSTRUCTION). |
| |
| 8. ADVISORY ONLY, SEPARATE PERMITS ARE REQUIRED FOR |
| PLUMBING, ELECTRICAL, MECHANICAL. |
| |
| **NOTE - CALL MICHELLE, PALM BEACH COUNTY IMPACT FEES, |
| TO CLARIFY SCOPE OF WORK FOR IMPACT FEE ASSESSMENT - |
| 233-5019** |
| |
| |
| |
| |