Plan Review Notes
Plan Review Notes For Permit 15081099
Permit Number 15081099
Review Stop E
Sequence Number 1
Notes
Date Text
2015-09-02 15:04:56PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. UNLESS PRIOR ARRANGEMENTS ARE MADE WITH THE
 ELECTRICAL INSPECTOR, ALL TRENCHING SHALL REMAIN OPEN
 FOR INSPECTION. NO SITE TUBES WILL BE ALLOWED. IF
 DIRECT BORING, HAVE THE CERTIFICATE OF COVER AVAILABLE
 FOR THE INSPECTOR. (THIS CAN BE ADDRESSED WITH A NOTE
 ON THE CORRECTED PLANS.)
 2. NEC 210.63 REQUIRES THAT THERE BE A SERVICE OUTLET
 WITHIN 25 FEET OF THE HVAC UNIT. INCLUDE THAT ON THE
 NEW RESIDED DRAWINGS.
 3. ALL WIRING SHALL BE REMOVED FROM EVERY ABANDONED
 OUTLET AS PRESCRIBED IN NEC 372.13.
 4. THE REMAINS OF THE FEEDER RACEWAY TO PANEL "L35"
 SHALL BE SEALED AT BOTH ENDS.
 5. YOUR RISER DIAGRAM REFLECTS TWO METERS FOR PANEL
 "L35" CORRECT ACCORDINGLY.
 6. PROVIDE SITE SPECIFIC LOAD CALCS AND PANEL SCHEDULES
 FOR PANELS "L35" & "L1"
 7. NEW EXHAUST FANS APPEAR TO BE 2 POLE, YET THE
 CIRCUIT SCHEDULE FOR PANEL A REFLECTS A SINGLE CKT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  