2015-09-02 15:04:56 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| 1. UNLESS PRIOR ARRANGEMENTS ARE MADE WITH THE |
| ELECTRICAL INSPECTOR, ALL TRENCHING SHALL REMAIN OPEN |
| FOR INSPECTION. NO SITE TUBES WILL BE ALLOWED. IF |
| DIRECT BORING, HAVE THE CERTIFICATE OF COVER AVAILABLE |
| FOR THE INSPECTOR. (THIS CAN BE ADDRESSED WITH A NOTE |
| ON THE CORRECTED PLANS.) |
| 2. NEC 210.63 REQUIRES THAT THERE BE A SERVICE OUTLET |
| WITHIN 25 FEET OF THE HVAC UNIT. INCLUDE THAT ON THE |
| NEW RESIDED DRAWINGS. |
| 3. ALL WIRING SHALL BE REMOVED FROM EVERY ABANDONED |
| OUTLET AS PRESCRIBED IN NEC 372.13. |
| 4. THE REMAINS OF THE FEEDER RACEWAY TO PANEL "L35" |
| SHALL BE SEALED AT BOTH ENDS. |
| 5. YOUR RISER DIAGRAM REFLECTS TWO METERS FOR PANEL |
| "L35" CORRECT ACCORDINGLY. |
| 6. PROVIDE SITE SPECIFIC LOAD CALCS AND PANEL SCHEDULES |
| FOR PANELS "L35" & "L1" |
| 7. NEW EXHAUST FANS APPEAR TO BE 2 POLE, YET THE |
| CIRCUIT SCHEDULE FOR PANEL A REFLECTS A SINGLE CKT. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |