2015-08-31 14:06:58 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | 1) SHEET A3.1, THE DOOR SCHEDULE INDICATES NORMAL | | HARDWARE ON THE DOOR # 1, RECEPTION. THIS IS A REQUIRED | | EXIT DOOR FOR AN OCCUPANCY GREATER THAN 100 AND PANIC | | HARDWARE IS REQUIRED. ENSURE PANIC HARDWARE IS | | INSTALLED AND THE DOOR CAN NOT BE LOCKED AGAINST | | EGRESS. | | | | 2) SHEET E2.1, ADD TWO (2) EXIT LIGHTS OVER DOOR # 1, | | RECEPTION AND DOOR EX3, PROGRAMMING. | | | | 3) FIRE INSPECTOR SHALL VERIFY ON FINAL INSPECTION. |
|