2015-08-25 19:11:37 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE RAS 117 CALCULATIONS ARE FOR EXPOSURE CATEGORY | | B. GROUND SURFACE ROUGHNESS C PREVAILS IN THE 1,500 | | FEET UPWIND DIRECTION TO THE NORTHWEST OF THE | | STRUCTURE. THEREFORE, EXPOSURE CATEGORY C APPLIES TO | | THIS STRUCTURE. FBC 1609.4.3 |
|