2015-08-26 10:41:50 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT 2 SETS OF SIGNED AND SEALED RAS 117 | | CALCULATIONS FOR ENHANCED FASTENING FROM A LICENSED | | DESIGN PROFESSIONAL AS REQUIRED BY LIMITATION NUMBER 7 | | ON PAGE 29 OF THE PRODUCT APPROVAL. ( NOA NO. | | 14-0611.01 ) FBC 107.2.1.3 | | | | 2) IT IS NOT CLEAR FROM THE APPLICATION IF THE TWO NEW | | SKYLIGHTS ARE REPLACING EXISTING ONES OR ARE NEW | | INSTALLATIONS. A ROOFING CONTRACTOR CAN REPLACE | | EXISTING SKYLIGHTS, BUT CAN NOT CUT AND FRAME OPENINGS | | TO INSTALL NEW ONES. PLEASE CLARIFY. FS 489 |
|