Plan Review Notes
Plan Review Notes For Permit 15080942
Permit Number 15080942
Review Stop M
Sequence Number 1
Notes
Date Text
2015-08-27 07:00:491ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080942
 8/27/15
  
 1) SUBMIT TWO SETS OF AC LOAD CALCULATIONS FOR THE NEW
 MINI-SPLIT SYSTEM- SEE SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION: CALCULATION OF HEATING AND COOLING LOADS.
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND
 COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD
 REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY
 SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE
 WITH THE ASHRAEHVAC SYSTEMS AND EQUIPMENT HANDBOOK.
 ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN
 APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE
 DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
 2) PROVIDE A PLAN SHOWING THE LOCATIONS OF THE OUTDOOR
 AND INDOOR UNITS AND INCLUDE TIE DOWN ENGINEERING FOR
 THE CONDENSER, AND A CONDENSATE DISPOSAL PLAN FOR THE
 AIR HANDLER- SECTION 301.15 AND 307 FBC-14 MECHANICAL.
 3) PROVIDE AN ELECTRICAL PLAN AND SUB-PERMIT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  