Plan Review Notes For Permit 15080892 |
Permit Number |
15080892 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-10-14 18:21:18 | ****CORRECTIONS**** | | REVISED 9/16 | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FROM PREVIOUS LIST: | | | | 3. IF ANY DOORS ARE EXTERIOR DOORS, AND IF THE BUILDING | | IS GREATER THAN 60FEET, DESIGN PRESSURES TO BE | | DETERMINED BY A DESIGN PROFESSIONAL, FBC 1609 | | (ASCE7-10), FS 471, 481. | | | | ENGINEER'S PLAN STATES TO SEE THE DOOR SPEC SHEETS FOR | | DP LIMITATIONS. | | | | ENGINEER TO STATE THE DESIGN PRESSURE REQUIREMENT FOR | | THE BUILDING. THE DOOR PRODUCT APPROVAL IS TO COMPLY | | WITH THE DESIGN PRESSURE REQUIREMENT. REVISE THE PLAN, | | OR ADD A LETTER, WHICH STATES THE DESIGN PRESSURE | | REQUIREMENTS FOR THE EXTERIOR DOORS FOR THIS PROJECT. | | NOTE THAT THIS BUILDING APPEARS TO BE LOCATED IN | | EXPOSURE D. THE DP LIMITATION FOR THE PROPOSED DOORS IS | | +65 / -53.3. | | | | | | |
|