Plan Review Notes
Plan Review Notes For Permit 15080892
Permit Number 15080892
Review Stop B
Sequence Number 1
Notes
Date Text
2015-08-29 11:07:49****CORRECTIONS****
 REVISED 9/16
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A PLAN SHOWING LOCATION OF PROPOSED DOORS,
 FIRE RATING OF PROPOSED DOORS, AND FIRE RATING FOR THE
 WALLS.
  
 NOT ENOUGH INFORMATION WAS PROVIDED TO PERFORM A PLAN
 REVIEW, FBC 107.
  
 PLAN SHOULD SHOW LOCATION OF DOORS, ALL FIRE RATED
 WALLS (ALL APPLICABLE SEPARATIONS SUCH AS FIRE PUMP
 ROOMS, ELECTRICAL ROOMS, STORAGE AS WELL AS OCCUPANCY
 SEPARATION, ETC.). SEE FBC CHAPTERS 5, 7.
  
 2. FBC 107, THE PLAN IS TO INCLUDE THE PRINTED NAME AND
 SIGNATURE OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR
 THE INFORMATION AND DESIGN. A DESIGN PROFESSIONAL MAY
 BE REQUIRED, FS471, 481.229(C).
  
 3. IF ANY DOORS ARE EXTERIOR DOORS, AND IF THE BUILDING
 IS GREATER THAN 60FEET, DESIGN PRESSURES TO BE
 DETERMINED BY A DESIGN PROFESSIONAL, FBC 1609
 (ASCE7-10), FS 471, 481.
  
  