2015-08-26 08:39:07 | APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL | | RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF | | RE-INSPECTION FEE(S). | | 1) PROVIDE AT LEAST ONE GFCI PROTECTED RECEPTACLE | | LOCATED A MINIMUM OF 6 FEET FROM AND NOT MORE THAN 20 | | FEET FROM THE INSIDE WALL OF THE POOL. FBCR - E4203.1.2 | | | | 2) BOND ALL FIXED METAL PARTS WITHIN 5 FEET OF THE | | INSIDE WALL OF THE POOL. FBCR - E4204.2 (7) | | | | 3) POOL WATER SHALL BE INTENTIONALLY BONDED IN | | ACCORDANCE WITH INSIDE WALL OF THE POOL. FBCR - E4204.3 |
|