Plan Review Notes
Plan Review Notes For Permit 15080857
Permit Number 15080857
Review Stop E
Sequence Number 1
Notes
Date Text
2015-08-26 08:39:07APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF
 RE-INSPECTION FEE(S).
 1) PROVIDE AT LEAST ONE GFCI PROTECTED RECEPTACLE
 LOCATED A MINIMUM OF 6 FEET FROM AND NOT MORE THAN 20
 FEET FROM THE INSIDE WALL OF THE POOL. FBCR - E4203.1.2
  
 2) BOND ALL FIXED METAL PARTS WITHIN 5 FEET OF THE
 INSIDE WALL OF THE POOL. FBCR - E4204.2 (7)
  
 3) POOL WATER SHALL BE INTENTIONALLY BONDED IN
 ACCORDANCE WITH INSIDE WALL OF THE POOL. FBCR - E4204.3