Plan Review Notes For Permit 15080832 |
Permit Number |
15080832 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2016-03-09 10:38:47 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | | | | | - NEC 210.8 A2 ALL GARAGES AND BATHROOMS OUTLETS SHALL | | BE GFCI PROTECTED. | | | | - NEC 212.52 SINCE CONVERTING GARAGE TO LIVABLE SPACE | | RECEPTACLES MUST SPACED 6FT IN BETWEEN EACH OTHER ON | | THE FLOOR PLANS. FURTHER MORE ANY SPACE 2FT OR MORE | | UNBROKEN BY OPENINGS SHALL HAVE A RECEPTACLE ON FLOOR | | PLANS. | | | | - NEC 210.70 2B A LIGHT IS REQUIRED OUTSIDE EVERY DOOR | | FOR SECURITY ILLUMINATION PURPOSES. | | | | PLEASE ADDRESS THESE COMMENTS ACCORDINGLY TO AVOID A 4X | | THE REVIEW FEE PENALTY. |
|