2015-12-07 17:46:59 | RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND BUILDING |
| REVIEW CHECKLIST. |
| CODE: FBC-5TH EDITION (2014). |
| |
| NOTE: |
| SEE ZONING COMMENTS REGARDING BUILDING SETBACKS. IN |
| ADDITION, SEE COMMENTS BELOW. |
| |
| 1- BASED ON SURVEY SUBMITTED, THE ADDITION IS LOCATED |
| LESS THAN 3'-0" FROM THE PROPERTY LINE. NEED TO COMPLY |
| WITH THE FOLLOWING: |
| A) NO OPENINGS ALLOWED. SEC. R302.1 AND TABLE R302.1(1) |
| OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| B) NEED TO SPECIFY 1 HR FIRE RATED EXTERIOR WALL |
| ASSEMBLY. SPECIFY PUBLISHED ASSEMBLY NUMBER. ASSEMBLY |
| SPECIFIED TO BE TESTED IN ACCORDANCE WITH ASTM E 119 OR |
| UL 263 WITH EXPOSURE ON BOTH SIDES. SEC. R302.1 AND |
| TABLE R302.1(1) OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| C) SPECIFY 1 HR FIRE RATED ASSEMBLY FOR THE UNDERSIDE |
| OF THE ROOF PROJECTION AS REQUIRED BY SEC. R302.1 AND |
| TABLE R302.1(1) OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| D) WALL PENETRATIONS NEED TO COMPLY WITH SEC. R302.1 |
| AND TABLE R302.1(1) OF FBC-RESIDENTIAL, 5TH EDITION |
| (2014). |
| |
| 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A) EXTERIOR DOOR. PROVIDE THE FLORIDA PRODUCT APPROVAL |
| COVER PAGE THAT CORRESPONDS TO DOOR DRAWINGS SUBMITTED. |
| NOTE: NEED FLORIDA PRODUCT APPROVAL COVER PAGE FOR 2014 |
| CODE. |
| RESPONSE: PRODUCT APPROVAL INFORMATION SUBMITTED |
| DOESN'T HAVE A FLORIDA PRODUCT APPROVAL COVER PAGE OR |
| FLORIDA PRODUCT APPROVAL NUMBER THAT CORRESPONDS TO |
| DRAWINGS SUBMITTED. AND, DRAWINGS SUBMITTED DON'T MATCH |
| TYPE OF DOOR SHOWN ON PLANS. |
| |
| B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ALL |
| DETAILS. PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE |
| AND PAGE SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO |
| LIST THE 2014 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO |
| EACH SPECIFIED CONNECTOR. |
| RESPONSE: CLEARLY SPECIFY FLORIDA PRODUCT APPROVAL |
| NUMBER FOR EACH CONNECTOR SPECIFIED ON THE WALL SECTION |
| "A" , INCLUDING THE SIMPSON 5P2 . ALSO, THERE ARE OTHER |
| CONNECTORS LIKE THE SIMPSON HTU28 THAT ARE NOT COVERED |
| UNDER THE FLORIDA PRODUCT APPROVAL FL10865. REVISE AS |
| REQUIRED. |
| |
| 3- ENGINEER OF RECORD TO APPROVE IN WRITING ALL PRODUCT |
| APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| AMENDMENTS. |
| RESPONSE: DOOR PRODUCT APPROVAL APPROVED BY THE |
| ENGINEER DOESN'T MATCH PLANS. |
| |
| 4- THERE ARE TWO DIFFERENT SURVEYS SUBMITTED. PLANS AND |
| SURVEY SUBMITTED DON'T MATCH. REVISE AS REQUIRED. |
| PROVIDE CLEAR DRAWINGS SHOWN WHAT'S EXISTING AND WHAT'S |
| PROPOSED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |