Plan Review Notes
Plan Review Notes For Permit 15080832
Permit Number 15080832
Review Stop B
Sequence Number 2
Notes
Date Text
2015-12-07 17:46:59RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
 NOTE:
 SEE ZONING COMMENTS REGARDING BUILDING SETBACKS. IN
 ADDITION, SEE COMMENTS BELOW.
  
 1- BASED ON SURVEY SUBMITTED, THE ADDITION IS LOCATED
 LESS THAN 3'-0" FROM THE PROPERTY LINE. NEED TO COMPLY
 WITH THE FOLLOWING:
 A) NO OPENINGS ALLOWED. SEC. R302.1 AND TABLE R302.1(1)
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) NEED TO SPECIFY 1 HR FIRE RATED EXTERIOR WALL
 ASSEMBLY. SPECIFY PUBLISHED ASSEMBLY NUMBER. ASSEMBLY
 SPECIFIED TO BE TESTED IN ACCORDANCE WITH ASTM E 119 OR
 UL 263 WITH EXPOSURE ON BOTH SIDES. SEC. R302.1 AND
 TABLE R302.1(1) OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 C) SPECIFY 1 HR FIRE RATED ASSEMBLY FOR THE UNDERSIDE
 OF THE ROOF PROJECTION AS REQUIRED BY SEC. R302.1 AND
 TABLE R302.1(1) OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 D) WALL PENETRATIONS NEED TO COMPLY WITH SEC. R302.1
 AND TABLE R302.1(1) OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) EXTERIOR DOOR. PROVIDE THE FLORIDA PRODUCT APPROVAL
 COVER PAGE THAT CORRESPONDS TO DOOR DRAWINGS SUBMITTED.
 NOTE: NEED FLORIDA PRODUCT APPROVAL COVER PAGE FOR 2014
 CODE.
 RESPONSE: PRODUCT APPROVAL INFORMATION SUBMITTED
 DOESN'T HAVE A FLORIDA PRODUCT APPROVAL COVER PAGE OR
 FLORIDA PRODUCT APPROVAL NUMBER THAT CORRESPONDS TO
 DRAWINGS SUBMITTED. AND, DRAWINGS SUBMITTED DON'T MATCH
 TYPE OF DOOR SHOWN ON PLANS.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ALL
 DETAILS. PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO
 LIST THE 2014 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO
 EACH SPECIFIED CONNECTOR.
 RESPONSE: CLEARLY SPECIFY FLORIDA PRODUCT APPROVAL
 NUMBER FOR EACH CONNECTOR SPECIFIED ON THE WALL SECTION
 "A" , INCLUDING THE SIMPSON 5P2 . ALSO, THERE ARE OTHER
 CONNECTORS LIKE THE SIMPSON HTU28 THAT ARE NOT COVERED
 UNDER THE FLORIDA PRODUCT APPROVAL FL10865. REVISE AS
 REQUIRED.
  
 3- ENGINEER OF RECORD TO APPROVE IN WRITING ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
 RESPONSE: DOOR PRODUCT APPROVAL APPROVED BY THE
 ENGINEER DOESN'T MATCH PLANS.
  
 4- THERE ARE TWO DIFFERENT SURVEYS SUBMITTED. PLANS AND
 SURVEY SUBMITTED DON'T MATCH. REVISE AS REQUIRED.
 PROVIDE CLEAR DRAWINGS SHOWN WHAT'S EXISTING AND WHAT'S
 PROPOSED. SEC. 107.2.1 CITY AMENDMENTS.
  
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]