2015-10-02 17:29:10RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS.
 CODE: FBC-5TH EDITION (2014).
  
 1- PROVIDE SITE PLAN OR SURVEY WITH COMPLETE DIMENSIONS
 SHOWING LOCATION OF NEW ADDITION AND EXISTING HOUSE.
 SEC. 107.3.5.3(1). CITY AMENDMENTS.
  
 2- IDENTIFY THE NAME OF THE ROOM OF PROPOSED ADDITION.
 WHAT'S THE ROOM GOING TO BE USED FOR?. NEED TO IDENTIFY
 ROOM FOR PROPER PLAN REVIEW. IS THIS ROOM GOING TO BE
 USED FOR LIVING PURPOSES?. CLARIFY WHY THERE IS NOT A
 DOOR BETWEEN THE STORAGE ROOM AND THE NEW ADDITION.
 CLARIFY WHY IS THERE A BATHROOM IN THE NEW ROOM
 ADJACENT TO THE STORAGE ROOM. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $15,000. THE
 PERMIT FEE BALANCE IS $1453.60.
  
 4- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 THEN, BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 5- SPECIFY THE ROOF PITCH OF THE NEW ADDITION TO VERIFY
 COMPLIANCE WITH SHINGLES INSTALLATION ON THE PROPOSED
 SLOPE. SEC. R905.2.2 OF FBC-RESIDENTIAL , 5TH EDITION
 (2014).
  
 6- LETTERING ON THE "TYP. HEADERS IN DR. & WINDOW
 FRAMING" DETAIL ON SHEET 2 OF 2 IS TO SMALL AND IS NOT
 LEGIBLE. REVISE AS REQUIRED. PROVIDE BIGGER AND CLEAR
 LETTERING. SEC. 107.2.1.4 CITY AMENDMENTS.
  
 7- WALL SECTION "A" ON SHEET 2 OF 2:
 A) SPECIFY ROOF CROSS VENTILATION AS REQUIRED BY SEC.
 R806 OF FBC-RESIDENTIAL , 5TH EDITION (2014).
  
 B) SPECIFY FOOTING SIZE. SEC. R301 OF FBC-RESIDENTIAL ,
 5TH EDITION (2014).
 NOTE: COORDINATE WITH ITEM #7(C) AND #7(D) BELOW.
  
 C) SPECIFY THE 6" CLEARANCE FROM GRADE TO FINISH FLOOR
 AS REQUIRED BY SEC. R404.1.6 OF FBC-RESIDENTIAL , 5TH
 EDITION (2014).
  
 D) SPECIFY FOOTING TO BE 12" BELOW FINISHED GRADE AS
 REQUIRED BY SEC. R403.1.4 OF FBC-RESIDENTIAL , 5TH
 EDITION (2014).
  
 E) LENGTH OF RED HEAD ANCHOR SPECIFIED TO CONNECT THE
 BOTTOM PLATE TO THE CONCRETE SLAB IS NOT CLEAR. REVISE
 AS REQUIRED. SEC. 107.2.1.4 CITY AMENDMENTS.
  
 F) SPECIFY STUCCO THICKNESS AS REQUIRED BY TABLE
 R702.1(1) OF FBC-RESIDENTIAL , 5TH EDITION (2014).
  
 8-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) EXTERIOR DOOR. PROVIDE THE FLORIDA PRODUCT APPROVAL
 COVER PAGE THAT CORRESPONDS TO DOOR DRAWINGS SUBMITTED.
 NOTE: NEED FLORIDA PRODUCT APPROVAL COVER PAGE FOR 2014
 CODE.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ALL
 DETAILS. PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO
 LIST THE 2014 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO
 EACH SPECIFIED CONNECTOR.
  
 9- ENGINEER OF RECORD TO APPROVE IN WRITING ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 *** PLEASE PROVIDE ENGINEER RESPONSE LETTER ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
  