2015-10-02 17:29:10 | RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW |
| COMMENTS. |
| CODE: FBC-5TH EDITION (2014). |
| |
| 1- PROVIDE SITE PLAN OR SURVEY WITH COMPLETE DIMENSIONS |
| SHOWING LOCATION OF NEW ADDITION AND EXISTING HOUSE. |
| SEC. 107.3.5.3(1). CITY AMENDMENTS. |
| |
| 2- IDENTIFY THE NAME OF THE ROOM OF PROPOSED ADDITION. |
| WHAT'S THE ROOM GOING TO BE USED FOR?. NEED TO IDENTIFY |
| ROOM FOR PROPER PLAN REVIEW. IS THIS ROOM GOING TO BE |
| USED FOR LIVING PURPOSES?. CLARIFY WHY THERE IS NOT A |
| DOOR BETWEEN THE STORAGE ROOM AND THE NEW ADDITION. |
| CLARIFY WHY IS THERE A BATHROOM IN THE NEW ROOM |
| ADJACENT TO THE STORAGE ROOM. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. VALUATION WAS UPDATED TO $15,000. THE |
| PERMIT FEE BALANCE IS $1453.60. |
| |
| 4- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. |
| THEN, BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| THE UNIFIED LAND DEVELOPMENT CODE. |
| |
| 5- SPECIFY THE ROOF PITCH OF THE NEW ADDITION TO VERIFY |
| COMPLIANCE WITH SHINGLES INSTALLATION ON THE PROPOSED |
| SLOPE. SEC. R905.2.2 OF FBC-RESIDENTIAL , 5TH EDITION |
| (2014). |
| |
| 6- LETTERING ON THE "TYP. HEADERS IN DR. & WINDOW |
| FRAMING" DETAIL ON SHEET 2 OF 2 IS TO SMALL AND IS NOT |
| LEGIBLE. REVISE AS REQUIRED. PROVIDE BIGGER AND CLEAR |
| LETTERING. SEC. 107.2.1.4 CITY AMENDMENTS. |
| |
| 7- WALL SECTION "A" ON SHEET 2 OF 2: |
| A) SPECIFY ROOF CROSS VENTILATION AS REQUIRED BY SEC. |
| R806 OF FBC-RESIDENTIAL , 5TH EDITION (2014). |
| |
| B) SPECIFY FOOTING SIZE. SEC. R301 OF FBC-RESIDENTIAL , |
| 5TH EDITION (2014). |
| NOTE: COORDINATE WITH ITEM #7(C) AND #7(D) BELOW. |
| |
| C) SPECIFY THE 6" CLEARANCE FROM GRADE TO FINISH FLOOR |
| AS REQUIRED BY SEC. R404.1.6 OF FBC-RESIDENTIAL , 5TH |
| EDITION (2014). |
| |
| D) SPECIFY FOOTING TO BE 12" BELOW FINISHED GRADE AS |
| REQUIRED BY SEC. R403.1.4 OF FBC-RESIDENTIAL , 5TH |
| EDITION (2014). |
| |
| E) LENGTH OF RED HEAD ANCHOR SPECIFIED TO CONNECT THE |
| BOTTOM PLATE TO THE CONCRETE SLAB IS NOT CLEAR. REVISE |
| AS REQUIRED. SEC. 107.2.1.4 CITY AMENDMENTS. |
| |
| F) SPECIFY STUCCO THICKNESS AS REQUIRED BY TABLE |
| R702.1(1) OF FBC-RESIDENTIAL , 5TH EDITION (2014). |
| |
| 8-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A) EXTERIOR DOOR. PROVIDE THE FLORIDA PRODUCT APPROVAL |
| COVER PAGE THAT CORRESPONDS TO DOOR DRAWINGS SUBMITTED. |
| NOTE: NEED FLORIDA PRODUCT APPROVAL COVER PAGE FOR 2014 |
| CODE. |
| |
| B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ALL |
| DETAILS. PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE |
| AND PAGE SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO |
| LIST THE 2014 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO |
| EACH SPECIFIED CONNECTOR. |
| |
| 9- ENGINEER OF RECORD TO APPROVE IN WRITING ALL PRODUCT |
| APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| AMENDMENTS. |
| |
| *** PLEASE PROVIDE ENGINEER RESPONSE LETTER ADDRESSING |
| EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |