2015-09-08 07:54:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLAN HAS BEEN REVISED BUT IT DOES NOT APPEAR THAT
 ALL ITEMS INCLUDED ON THE VIOLATION / STOP WORK ORDER
 ISSUED ARE INCLUDED IN THE PLAN, FBC 105, FBC 107. WORK
 WILL BE CONFIRMED BY THE INSPECTOR WHO ISSUED THE
 VIOLATION.
  
 2. VALUE WILL BE DETERMINED WHEN SCOPE OF WORK HAS BEEN
 ESTABLISHED, FBC 109.
  
 3. ELECTRICAL PERMIT REQUIRED, FBC 107. PROVIDE AN
 ELECTRICAL PERMIT APPLICATION. THE RESPONSE LETTER
 STATES THAT "NO ELECTRICAL WORK INCLUDED IN OUR SCOPE
 OF WORK."
  
 A RENOVATION WHICH INCLUDED BUILDING, PLUMBING, AND
 ELECTRICAL WAS STARTED WITHOUT A PERMIT. PLEASE SEE FBC
 5TH EDITION EXISTING BUILDING CODE SECTIN 301.1; A
 METHOD OF COMPLIANCE IS TO BE SELECTED. UNTIL ENTIRE
 SCOPE OF WORK IS DETERMINED, LEVEL OF ALTERATION OR
 OTHER METHOD OF COMPLIANCE CANNOT BE DETERMINED (AND
 HAS NOT BEEN STATED BY UNKNOWN DESIGNER WHO PREPARED
 THE PLAN).
  
 IF THIS CONTRACTOR WILL NOT TAKE RESPONSIBILITY FOR THE
 WORK DONE AND WORK PROPOSED, ANOTHER CONTRACTOR
 LICENSED TO DO SO IS REQUIRED.
  
 4. THE PRINTED NAME AND SIGNATURE OF THE INDIVIDUAL
 TAKING RESPONSIBILITY FOR THE DESIGN IS TO BE ON THE
 PLAN, FBC 107.
  
  
  
  
  
  
  
  