Plan Review Notes For Permit 15080826 |
Permit Number |
15080826 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-09-08 07:54:16 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. PLAN HAS BEEN REVISED BUT IT DOES NOT APPEAR THAT | | ALL ITEMS INCLUDED ON THE VIOLATION / STOP WORK ORDER | | ISSUED ARE INCLUDED IN THE PLAN, FBC 105, FBC 107. WORK | | WILL BE CONFIRMED BY THE INSPECTOR WHO ISSUED THE | | VIOLATION. | | | | 2. VALUE WILL BE DETERMINED WHEN SCOPE OF WORK HAS BEEN | | ESTABLISHED, FBC 109. | | | | 3. ELECTRICAL PERMIT REQUIRED, FBC 107. PROVIDE AN | | ELECTRICAL PERMIT APPLICATION. THE RESPONSE LETTER | | STATES THAT "NO ELECTRICAL WORK INCLUDED IN OUR SCOPE | | OF WORK." | | | | A RENOVATION WHICH INCLUDED BUILDING, PLUMBING, AND | | ELECTRICAL WAS STARTED WITHOUT A PERMIT. PLEASE SEE FBC | | 5TH EDITION EXISTING BUILDING CODE SECTIN 301.1; A | | METHOD OF COMPLIANCE IS TO BE SELECTED. UNTIL ENTIRE | | SCOPE OF WORK IS DETERMINED, LEVEL OF ALTERATION OR | | OTHER METHOD OF COMPLIANCE CANNOT BE DETERMINED (AND | | HAS NOT BEEN STATED BY UNKNOWN DESIGNER WHO PREPARED | | THE PLAN). | | | | IF THIS CONTRACTOR WILL NOT TAKE RESPONSIBILITY FOR THE | | WORK DONE AND WORK PROPOSED, ANOTHER CONTRACTOR | | LICENSED TO DO SO IS REQUIRED. | | | | 4. THE PRINTED NAME AND SIGNATURE OF THE INDIVIDUAL | | TAKING RESPONSIBILITY FOR THE DESIGN IS TO BE ON THE | | PLAN, FBC 107. | | | | | | | | | | | | | | | | |
|