2015-09-10 13:56:401ST REVIEW: FBC 2010 MECHANICAL
 REVISION #15080805
 MASTER #14050097
 9/10/15
  
 1) IN ORDER TO EXPEDITE THE REVIEW PROCESS, PLEASE
 SUBMIT A NARRATIVE THAT CLEARLY IDENTIFIES ALL THE
 REVISIONS THAT WERE MADE TO THE APPROVED MECHANICAL
 PLANS. IN ADDITION, PLEASE CLOUD ALL THE REVISIONS ON
 THE PLANS AND PROVIDE DELTA TRIANGLE SYMBOLS AT EACH
 REVISION LOCATION.
 2) SHEET M102 INDICATES A "NEW AHU-1.9" PROVIDE AN
 EQUIPMENT SCHEDULE FOR THE NEW UNIT AND CLARIFY IF THIS
 WAS JUST A SAME-SIZE REPLACEMENT, AR ACTUALLY A NEW AC
 UNIT. PLEASE NOTE THAT COOLING AND HEATING CALCULATIONS
 ARE REQUIRED FOR NEW SYSTEMS- REFER TO SECTION C403.2.1
 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER