Plan Review Notes
Plan Review Notes For Permit 15080805
Permit Number 15080805
Review Stop B
Sequence Number 1
Notes
Date Text
2015-09-26 13:55:02 
 BUILDING PLAN REVIEW
 W. P. B. REVISION: 15080805
 W. P. B. PERMIT: 14050097
 ADD: 8100 IBIS BLVD.
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. SEPT. 26/2015
 ACTION: DENIED
  
 1) SHEET GI102 LIFE SAFETY PLAN UPPER LEVEL, PLEASE
 REVIEW THE BAR TERRACE 214 WITH A OCCUPANT LOAD OF 167
 OCCUPANTS. WHEN OCCUPANT LOADS ARE GREATER THAN 49
 OCCUPANTS, 2 EXITS ARE REQUIED, TABLE 1015.1. THIS
 SHEET SHOWS THE 2ND MEANS OF EGRESS FROM THE TERRACE
 GOING BACK INSIDE THE BUILDING. SECTION 1027.1 STATES
 ONCE YOU HAVE LEFT THE EXIT YOU ARE IN THE EXIT
 DISCHARGE, THE EXIT DISCHARGE SHALL NOT REENTER THE
 BUILDING.
  
 2) SHEET GI102. THE FIRE REVIEW HAS ALSO POINTED OUT
 THE PINCH POINT AT THE MAIN ENTRY WHERE THE OCCUPANT
 LOAD OF 591 PERSONS WHICH EQUATES TO A REQUIRED EGRESS
 WIDTH OF 9FT. 10 1/4 INCHES. THE LOBBY ONLY HAS 8 FT 6
 INCHES IN WIDTH. 1005.1 MINIMUM REQUIRED EGRESS WIDTH.
  
 3) SHEET GI102. THE OTHER ISSUE IS 2 MEANS OF EGRESS
 FROM BOTH ROOMS 225 A & 225B WHEN MORE THAN 49 OCCUPANT
 ARE IN A ROOM, 2 EXIT ACCESS DOORWAYS ARE REQUIRED, IN
 A SPRINKLERED BUILDING THE DOORWAYS NEED TO BE 1/3RD OF
 THE OVERALL DIAGONAL DISTANCE APART. 1015.2.1 EXCEP. #
 2.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  