Plan Review Notes
Plan Review Notes For Permit 15080803
Permit Number 15080803
Review Stop M
Sequence Number 1
Notes
Date Text
2015-08-28 15:29:351ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080803
 8/28/15
  
 1) SHEET M-1: PROVIDE DETAILS FOR THE O/A AIR DUCT AND
 CHILLED WATER PIPE INSULATIONS- TYPES, THICKNESSES, AND
 R-VALUES: REFER TO TABLE C403.2.7.1 AND C403.2.8 FBC-14
 ENERGY CONSERVATION.
 2) M-2 & M-17: THE FLORIDA BUILDING CODE FIFTH EDITION
 2014 WENT INTO EFFECT ON JUNE 30, 2015. PLEASE UPDATE
 THE CODE REFERENCES ACCORDINGLY AND VERIFY THE DESIGN
 IS IN COMPLIANCE.
 3) M-5- M-10: REVIEW THE NEW WORK SECTIONS AND NOTES. I
 AM FINDING MANY NOTES MISSING FROM THE DRAWINGS SUCH AS
 NOTE #1, 3, 5, 11 ETC.
 4) M-12 & M21: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 RETURN AIR SYSTEM OF THE NEW OAU-1 PER SECTION 606.2.1
 FBC-14 MECHANICAL. PLEASE NOTE THAT LEVEL 1 ALTERATIONS
 SHALL COMPLY WITH THE CURRRENT 2014 FLORIDA BUILDING
 CODES- REFER TO SECTION 702.4 FBC-14 EXISTING BUILDING
 CODE.
 5) M-15: PROVIDE A SCHEDULE FOR THE PIPE HANGERS
 INDICATING THE REQUIRED SPACINGS PER PIPE DIAMETER, AND
 ANCHOR TYPES PER SUBSTRATE MATERIAL.
 6) M-16: REFER TO THE SMACNA HVAC DUCT CONSTRUCTION
 STANDARDS- 2005, AND SMACNA FIBROUS GLASS DUCT
 CONSTRUCTION STANDARDS- 2010. PROVIDE HANGER AND
 SUPPORT DETAILS FOR BOTH METAL AND FIBROUS DUCTS.
 7) THE CITY OF WPB CONSTRUCTION SERVICES AC CHANGE-OUT
 COMPLIANCE FORM: PROVIDE COPIES OF THE FORM IN
 DUPLICATE FOR THE AHU'S AND THE OAU-1.
 8) COMMISSSIONING: REFER TO SECTION C408 FBC-14 ENERGY
 COMPLIANCE. PLEASE PROVIDE A COMMISSIONING PLAN IN
 ACCORDANCE WITH C408.2.1. REVIEW ALL SUB-SECTIONS THAT
 ARE APPLICABLE TO THE PROPOSED PROJECT INCLUDING
 SECTION C408.2.4.1 FOR FINAL INSPECTION APPROVAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  