2015-09-14 16:05:50PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. PG. E5: LARGE VIEW 4: DS-AC 12 & DS-AC 14 APPEARS TO
 BE ENCROACHING THE SAFE WORKING CLEARANCE REQUIRED BY
 NEC 110.26.
 2. PG. E6: PER NEC 406.8, THE WP RECEPTACLE OUTDOORS ON
 THE ROOF SHALL ALSO BE LISTED AS WEATHER RESISTANT
 ?WR?.
 3. PG. E7: VERIFY THE ALLOTTED CLEARANCE ABOUT
 ELECTRICAL EQUIPMENT SPECIFIED IN NEC 110.26. MAIN
 ELECTRICAL ROOM APPEARS TO BE IN VIOLATION.
 THE OVER CURRENT PROTECTION FOR THE FPL FEEDER IS 200
 AMP. CORRECT ACCORDINGLY
 PROVIDE LOAD CALCS FOR PANEL ?L1? AND ?MSBD? TO
 ASCERTAIN PROPER ACCEPTANCE OF NEW LOADS.
 INDICATE CONDUCTOR SIZES FEEDING DISCONNECTS OFF OF
 PANEL L1 CIRCUITS 7 ? 10.
 DESCRIBE WHAT PART OF THE SCOPE INVOLVES PANEL ?F?.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  