2015-11-02 12:36:172ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
 1. TOILET CLEARANCE SHALL COMPLY WITH FBC ACC. 2014 SEC
 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR
 RIGHT-HAND APPROACH.
 2. GRAB BARS SHALL COMPLY WITH FBC ACC. 2014 SEC 609.4
 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, AND 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
 3.
 THE BTU LOADS LISTED ON THE EQUIPMENT SCHEDULE ARE NOT
 THE SAME AS THE ONES LISTED ON THE GAS LOAD CALCULATION
 DETAIL ON SHEET 3.1P AND THE BTU TOTALS ON THE RISER
 DON'T MATCH UP WITH THE GAS LOAD CALCULATION ALL BTU
 LOADS MUST MATCH BEFORE I CAN DO A COMPLETE GAS REVIEW.
 PER WPB AMEND. TO FBC SEC107.2.1
 4. SHEET 1.1A ON THE EQUIPMENT SCHEDULE # 12, 13 ARE
 MISSING THE GAS CONNECTION AND BTU PLEASE PROVIDE. PER
 WPB AMEND. TO FBC SEC107.2.1
 5. REGULATOR SHALL BE INSTALLED WITH VALVE AND CAP FOR
 FUTURE FIXTURES SHOW ON RISER. PER WPB AMEND. TO FBC
 SEC107.2.1
 6. TOILET IN MEN'S BATHROOM STILL MISSING FROM RISER.
 PER WPB AMEND. TO FBC SEC107.2.1
  
 7. VENT DETAIL FOR TANKLESS HEATER TO GENERIC PLEASE
 PROVIDE MANUFACTURE SPECS ALONG WITH SIZE LENGTH AND
 CONFIGURATION PER WPB AMEND. TO FBC SEC107.2.1
 8. SHEET 3.0P ON FLOOR PLAN IT SHOWS STORAGE TANK AS 50
 GAL ON WATER RISER IT'S SHOWN AS 40 GAL PLEASE CLARIFY.
 PER WPB AMEND. TO FBC SEC107.2.1
 9. THE WATER RISER DIAGRAM IS MISSING HOT AND COLD STUB
 OUTS FOR HAND SINK #44 ON SHEET 1.1A AND #34 ON SHEET
 1.1A PLEASE CLARIFY. PER WPB AMEND. TO FBC SEC107.2.1
  