2015-11-02 12:36:17 | 2ND REVIEW: FBC 2014 |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |
| |
| PLUMBING COMMENTS: |
| |
| |
| 1. TOILET CLEARANCE SHALL COMPLY WITH FBC ACC. 2014 SEC |
| 604.2 LOCATION. |
| THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM |
| TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR |
| PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17 |
| INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM |
| FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY |
| ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2. |
| WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR |
| RIGHT-HAND APPROACH. |
| 2. GRAB BARS SHALL COMPLY WITH FBC ACC. 2014 SEC 609.4 |
| POSITION OF GRAB BARS. |
| GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) |
| MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| THE GRIPPING SURFACE, AND 604.5.2 REAR WALL. |
| THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| 3. |
| THE BTU LOADS LISTED ON THE EQUIPMENT SCHEDULE ARE NOT |
| THE SAME AS THE ONES LISTED ON THE GAS LOAD CALCULATION |
| DETAIL ON SHEET 3.1P AND THE BTU TOTALS ON THE RISER |
| DON'T MATCH UP WITH THE GAS LOAD CALCULATION ALL BTU |
| LOADS MUST MATCH BEFORE I CAN DO A COMPLETE GAS REVIEW. |
| PER WPB AMEND. TO FBC SEC107.2.1 |
| 4. SHEET 1.1A ON THE EQUIPMENT SCHEDULE # 12, 13 ARE |
| MISSING THE GAS CONNECTION AND BTU PLEASE PROVIDE. PER |
| WPB AMEND. TO FBC SEC107.2.1 |
| 5. REGULATOR SHALL BE INSTALLED WITH VALVE AND CAP FOR |
| FUTURE FIXTURES SHOW ON RISER. PER WPB AMEND. TO FBC |
| SEC107.2.1 |
| 6. TOILET IN MEN'S BATHROOM STILL MISSING FROM RISER. |
| PER WPB AMEND. TO FBC SEC107.2.1 |
| |
| 7. VENT DETAIL FOR TANKLESS HEATER TO GENERIC PLEASE |
| PROVIDE MANUFACTURE SPECS ALONG WITH SIZE LENGTH AND |
| CONFIGURATION PER WPB AMEND. TO FBC SEC107.2.1 |
| 8. SHEET 3.0P ON FLOOR PLAN IT SHOWS STORAGE TANK AS 50 |
| GAL ON WATER RISER IT'S SHOWN AS 40 GAL PLEASE CLARIFY. |
| PER WPB AMEND. TO FBC SEC107.2.1 |
| 9. THE WATER RISER DIAGRAM IS MISSING HOT AND COLD STUB |
| OUTS FOR HAND SINK #44 ON SHEET 1.1A AND #34 ON SHEET |
| 1.1A PLEASE CLARIFY. PER WPB AMEND. TO FBC SEC107.2.1 |
| |