2015-11-04 17:04:32 | 2ND REVIEW: FBC 2014 MECHANICAL |
| PERMIT #15080784 |
| 11/4/2015 |
| |
| 1) SHEET 3.2M: THE O/A CALCULATIONS ARE INCORRECT. |
| REFER TO TABLE 403.3: 7.5 CFM PER PERSON + .18 CFM PER |
| SF. IS REQUIRED FOR THE DINING AREAS. PLEASE REVISE THE |
| VENTILATION AND AIR BALANCE SCHEDULES ACCORDINGLY. |
| 2) 3.2M: THE REVISED AC EQUIPMENT SCHEDULE INDICATES A |
| NEW 5-TON AC SYSTEM: REFER TO SECTION C403.2.1 FBC-14 |
| ENERGY CONSERVATION AND SUBMIT COOLING AND HEATING LOAD |
| CALCULATIONS IN ACCORDANCE WITH THE ASHRAE STANDARD 183 |
| OR ACCA MANUAL N. |
| 3) REFER TO SECTION C101.4.3 FBC-14 ENERGY CONSERVATION |
| AND PROVIDE ENERGY CALCULATIONS FOR THE PROPOSED |
| RENOVATION. SEE SECTION C101.5 FOR COMPLIANCE SUBMITTAL |
| INFORMATION. |
| 4) SHEETS 1.3A & 3.2M: INDICATE HOW ACCESS FOR SERVICE |
| WILL BE PROVIDED TO THE NEW AHU-1 ABOVE THE MEN'S ROOM |
| CEILING. THIS APPEARS TO BE A HARD CEILING ALTHOUGH IT |
| IS NOT LABELED ON THE RCP. IT IS ALSO NOT CLEAR HOW |
| ACCESS WILL BE PROVIDED FOR AHU'S 2 & 3. PLEASE NOTE |
| THAT CLEAR OPENINGS FOR ACCESS PANELS SHALL BE LARGE |
| ENOUGH TO REMOVE EQUIPMENT WITHOUT REMOVING PERMANENT |
| CONSTRUCTION- SECTION 306.1. |
| 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE F/S |
| DAMPER AT TTHE BOTTOM OF THE FIRE-RATED SHAFT WITH A |
| REVIEW AND APPROVAL STAMP FROM THE ENGINEER OF RECORD. |
| |