Plan Review Notes
Plan Review Notes For Permit 15080784
Permit Number 15080784
Review Stop M
Sequence Number 2
Notes
Date Text
2015-11-04 17:04:322ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080784
 11/4/2015
  
 1) SHEET 3.2M: THE O/A CALCULATIONS ARE INCORRECT.
 REFER TO TABLE 403.3: 7.5 CFM PER PERSON + .18 CFM PER
 SF. IS REQUIRED FOR THE DINING AREAS. PLEASE REVISE THE
 VENTILATION AND AIR BALANCE SCHEDULES ACCORDINGLY.
 2) 3.2M: THE REVISED AC EQUIPMENT SCHEDULE INDICATES A
 NEW 5-TON AC SYSTEM: REFER TO SECTION C403.2.1 FBC-14
 ENERGY CONSERVATION AND SUBMIT COOLING AND HEATING LOAD
 CALCULATIONS IN ACCORDANCE WITH THE ASHRAE STANDARD 183
 OR ACCA MANUAL N.
 3) REFER TO SECTION C101.4.3 FBC-14 ENERGY CONSERVATION
 AND PROVIDE ENERGY CALCULATIONS FOR THE PROPOSED
 RENOVATION. SEE SECTION C101.5 FOR COMPLIANCE SUBMITTAL
 INFORMATION.
 4) SHEETS 1.3A & 3.2M: INDICATE HOW ACCESS FOR SERVICE
 WILL BE PROVIDED TO THE NEW AHU-1 ABOVE THE MEN'S ROOM
 CEILING. THIS APPEARS TO BE A HARD CEILING ALTHOUGH IT
 IS NOT LABELED ON THE RCP. IT IS ALSO NOT CLEAR HOW
 ACCESS WILL BE PROVIDED FOR AHU'S 2 & 3. PLEASE NOTE
 THAT CLEAR OPENINGS FOR ACCESS PANELS SHALL BE LARGE
 ENOUGH TO REMOVE EQUIPMENT WITHOUT REMOVING PERMANENT
 CONSTRUCTION- SECTION 306.1.
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE F/S
 DAMPER AT TTHE BOTTOM OF THE FIRE-RATED SHAFT WITH A
 REVIEW AND APPROVAL STAMP FROM THE ENGINEER OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  