Plan Review Notes
Plan Review Notes For Permit 15080784
Permit Number 15080784
Review Stop E
Sequence Number 2
Notes
Date Text
2015-11-05 19:33:36THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 2010 FBC,
 (FLORIDA BUILDING CODE) AS APPLICABLE AND BELOW ARE THE
 DEFICIENCIES NOTED.
  
 THESE PLANS HAVE BEEN UNSUCCESSFULLY REVIEWED FOR
 COMPLIANCE A SECOND TIME. BE ADVISED THAT:
 PURSUANT TO FL ?553.80, THE 4TH SUBMITTAL FOR A PERMIT
 WHICH REFLECTS FAILURE TO CORRECT A DEFICIENCY
 PREVIOUSLY SPECIFICALLY AND CONSISTENTLY IDENTIFIED ON
 ALL PRIOR SUBMITTALS MUST RESULT IN THE ASSESSMENT OF A
 PENALTY OF 3 TIMES THE PLAN REVIEW FEE IN ADDITION TO
 THE NORMAL FEE
  
 1. PLEASE NUMBER YOUR PAGES IN A USUAL AND CUSTOMARY
 MANNER WHERE THERE ARE SPECIFIC SECTIONS FOR THE
 VARIOUS TRADES; EACH OF WHICH COMMENCES WITH A SHEET 1
 SO AS NOT TO BE CONFUSED WITH WHAT APPEARS TO BE AN
 INCOMPLETE SET OF PLANS. AS IT IS, YOU ARE MISSING PAGE
 2.2E SUPPOSEDLY THE ROOF LAY OUT OF THE ELECTRICAL AND
 MECHANICAL EQUIPMENT.
 2. YOU SHALL PROVIDE BUILDING ELEVATIONS FOR BOTH THE
 FRONT AND BREEZEWAY FACADES TO ASCERTAIN WHAT IS
 SUPPOSEDLY A DOOR OR A WINDOW.
 3. PROVIDE WALL SECTIONS TO INDICATE WHICH ARE GLASS
 CURTAIN WALLS IF ANY.
 4. CONTRARY TO THE SUBMITTED RESPONSE, GENERAL NOTES 1,
 CONTINUE TO MAKE REFERENCE TO A NON-EXISTENT CODE.
 CORRECT THE NOTE ACCORDINGLY.
 5. NEC 300.5: AMBIENT CONDITIONS DICTATE CONDUCTOR
 INSULATION, NOT THE AWG GAUGE. PER CODE THWN INSULATION
 IS REQUIRED IN WET LOCATIONS. CORRECT YOUR ELECTRICAL
 NOTE 12 ACCORDINGLY.
 6. NEC 406.9(B): ALL OUTLETS IN WET LOCATIONS IN
 ADDITION TO HAVE WEATHER-PROOF COVERS SHALL BE LISTED
 ?WR? WEATHER-RESISTANT. CORRECT YOU ELECTRICAL NOTE 20
 ACCORDINGLY.
 7. NEC 600.5 REQUIRES A DEDICATED SIGN OUTLET AT EVERY
 PEDESTRIAN ENTRY. THE PREVIOUS COMMENTS NEVER ASKED IF
 THE EXISTING SIGNS WERE LIT OR NOT, THEY ADDRESSED THE
 CODE REQUIREMENTS WHICH YOU FAILED TO ADHERE TO.
 8. NEC 210.62: CONTRARY TO YOUR RESPONSE TO MY
 COMMENTS, YOU FAIL TO SHOW THE ?SHOW WINDOW? OUTLETS
 YOU INDICATED ON THE NORTH ELEVATION.
 9. ALL CORRECTIONS SHALL BE CLOUDED FOR IDENTIFICATION
 AND AS INSTRUCTED BELOW THE NEW PAGES INSERTED INTO THE
 PLANS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  