Plan Review Notes For Permit 15080784 |
Permit Number |
15080784 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-09-02 08:31:22 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #15080784 | | 9/2/15 | | | | 1) SHEET 3.2M: REFER TO TABLE 403.3 FBC-14 MECHANICAL | | AND SHOW THE CALCULATIONS FOR THE OUTSIDE AIR CFM'S | | LISTED IN THE EQUIPMENT SCHEDULE, PROVIDE A SCHEDULE | | THAT LISTS THE REQUIRED AND PROVIDED CFM'S FOR EACH | | ROOM, SPACE, OR AREA. | | 2) 3.2M: PROVIDE AN AIR BALANCE SCHEDULE. | | 3) 3.2M: THE EF2 'S SHOWN IN THE TOILET ROOMS ARE | | LISTED AS HEAT HOOD EXHAUST FANS IN THE SCHEDULE- | | PLEASE CORRECT. | | 4) 3.2M: PROVIDE THE WIND LOAD DESIGN CRITERIA AND | | PRESSURES FOR INSTALLATION OF THE ROOF-MOUNTED | | CONDENSER AND STAND- SECTION 301.15. SUBMIT TWO COPIES | | OF THE FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA FOR | | THE RM ENTERPRISES ROOF STAND. | | 5) 3.2M: PROVIDE DUCT HANGING AND CONNECTION DETAILS. | | 6) 3.2M: PLEASE ENLARGE THE SEPARATE PERMIT NOTE FOR | | THE KITCHEN HOODS-, AND ADD BOTH THE GREASE AND HEAT | | HOODS, AND THE WALK IN COOLER TO THE NOTE. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|