2015-09-02 08:31:221ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080784
 9/2/15
  
 1) SHEET 3.2M: REFER TO TABLE 403.3 FBC-14 MECHANICAL
 AND SHOW THE CALCULATIONS FOR THE OUTSIDE AIR CFM'S
 LISTED IN THE EQUIPMENT SCHEDULE, PROVIDE A SCHEDULE
 THAT LISTS THE REQUIRED AND PROVIDED CFM'S FOR EACH
 ROOM, SPACE, OR AREA.
 2) 3.2M: PROVIDE AN AIR BALANCE SCHEDULE.
 3) 3.2M: THE EF2 'S SHOWN IN THE TOILET ROOMS ARE
 LISTED AS HEAT HOOD EXHAUST FANS IN THE SCHEDULE-
 PLEASE CORRECT.
 4) 3.2M: PROVIDE THE WIND LOAD DESIGN CRITERIA AND
 PRESSURES FOR INSTALLATION OF THE ROOF-MOUNTED
 CONDENSER AND STAND- SECTION 301.15. SUBMIT TWO COPIES
 OF THE FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA FOR
 THE RM ENTERPRISES ROOF STAND.
 5) 3.2M: PROVIDE DUCT HANGING AND CONNECTION DETAILS.
 6) 3.2M: PLEASE ENLARGE THE SEPARATE PERMIT NOTE FOR
 THE KITCHEN HOODS-, AND ADD BOTH THE GREASE AND HEAT
 HOODS, AND THE WALK IN COOLER TO THE NOTE.
  
 CHRISTOPHER L. COLE