2015-10-06 13:30:04 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE |
| ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH |
| REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE |
| REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED |
| SHALL BE RESUBMITTED FOR ANOTHER REVIEW. |
| |
| 1. YOU INCORRECTLY REFERENCE THE 2010 NEC. THE |
| APPLICABLE EDITION IS THE 2011 NEC; THERE NEVER WAS A |
| 2010 EDITION. |
| 2. YOU SHALL PROVIDE A DEDICATED SIGN OUTLET ABOVE |
| EVERY PEDESTRIAN ENTRY, AS REQUIRED PER NEC 600.5 |
| 3. YOU SHALL PROVIDE A DEDICATED SHOW WINDOW RECEPTACLE |
| FOR EVERY 12 LINEAR FT. OR PORTION THEREOF OF SHOW |
| WINDOW, PER NEC 210.62 |
| 4. YOU SHALL INDICATE ON THE LIGHTING PLAN WHAT FIXTURE |
| ARRANGEMENTS OR PROVISIONS HAVE BEEN MADE THE REQUIRED |
| EMERGENCY LIGHTING. |
| 5. YOU SHALL SUBMIT A LIGHT DENSITY CHART AND INDICATE |
| COMPLIANCE WITH THE FBC-ENERGY CONSERVATION CODE |
| SECTION C405. |
| 6. THERE IS A MISSING EXIT LIGHT AS MARKED ON THE |
| LIGHTING FLOOR PLAN. |
| 7. THERE IS AN EXIT LIGHT THAT HAS TO BE RELOCATED |
| ABOVE THE CORRESPONDING DOOR. |
| 8. THE PANEL SCHEDULES DO NOT MATCH THE FLOOR PLAN |
| CIRCUIT DESIGNATION. |
| 9. INDICATE THE LOCATION OF ALL THE HVAC EQUIPMENT ON |
| THE FLOOR PLAN. |
| 10. IF THE ALARM CIRCUIT INDICATED ON PANEL A, 19 IS |
| FOR A FIRE ALARM SYSTEM, ADDITIONAL REQUIREMENTS ARE |
| NECESSARY. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU |
| |