2015-09-01 07:19:14 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #15080764 | | 9/1/2015 | | | | 1) THE PROPOSED PROJECT IS CLASSIFIED AS A LEVEL 2 | | ALTERATION IN ACCORDANCE WITH SECTION 504.1 FBC-14 | | EXISTING BUILDING. REFER TO SECTION 809.2 ALTERED | | EXISTING SYSTEMS. | | IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL | | VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR | | EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER | | MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR | | AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION | | AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF | | VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY | | PROCEDURE OF ASHRAE 62. PLEASE PROVIDE CALCULATIONS | | INDICATING COMPLIANCE, AND INDICATE THE SUPPLY CFM'S AT | | EACH DIFFUSER LOCATION. | | 2) PROVIDE RETURN AIR SYSTEM DETAILS ON THE PLAN- | | LOCATION AND SIZES OF RETURN DUCTS, GRILLS, CFM'S. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|