2015-09-08 17:42:58PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. INDICATE IF THE S/D INSIDE THE 1ST FLR. ELECTRIC
 ROOM NEW OR EXISTING? IT IS NOT MARKED AS EXISTING NOR
 INCLUDED ON THE RISER DIAGRAM.
 2. INDICATE IF THE S/D INSIDE THE 1ST FLR. CORRIDOR,
 ADJACENT TO THE EVAC PANEL NEW OR EXISTING? IT IS NOT
 MARKED AS EXISTING NOR INCLUDED ON THE RISER DIAGRAM.
 3. INDICATE IF THE D/D, RT & CM FOR RTU 4 ON THE ROOF
 ARE NEW OR EXISTING? THEY'RE NOT MARKED AS EXISTING NOR
 INCLUDED ON THE RISER DIAGRAM.
 4. INDICATE IF THE D/D, RT & CM IN THE BALCONY ARE FOR
 RTU 3 AND IF THEY ARE NEW OR EXISTING? THEY'RE NOT
 MARKED AS EXISTING NOR INCLUDED ON THE RISER DIAGRAM.
 5. IDENTIFY YOUR LINE WEIGHT/STYLE ON THE RISER DIAGRAM
 TO INDICATE THE NEW VS. THE EXISTING RUNS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  