2015-09-08 17:42:58 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| |
| 1. INDICATE IF THE S/D INSIDE THE 1ST FLR. ELECTRIC |
| ROOM NEW OR EXISTING? IT IS NOT MARKED AS EXISTING NOR |
| INCLUDED ON THE RISER DIAGRAM. |
| 2. INDICATE IF THE S/D INSIDE THE 1ST FLR. CORRIDOR, |
| ADJACENT TO THE EVAC PANEL NEW OR EXISTING? IT IS NOT |
| MARKED AS EXISTING NOR INCLUDED ON THE RISER DIAGRAM. |
| 3. INDICATE IF THE D/D, RT & CM FOR RTU 4 ON THE ROOF |
| ARE NEW OR EXISTING? THEY'RE NOT MARKED AS EXISTING NOR |
| INCLUDED ON THE RISER DIAGRAM. |
| 4. INDICATE IF THE D/D, RT & CM IN THE BALCONY ARE FOR |
| RTU 3 AND IF THEY ARE NEW OR EXISTING? THEY'RE NOT |
| MARKED AS EXISTING NOR INCLUDED ON THE RISER DIAGRAM. |
| 5. IDENTIFY YOUR LINE WEIGHT/STYLE ON THE RISER DIAGRAM |
| TO INDICATE THE NEW VS. THE EXISTING RUNS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |