Plan Review Notes
Plan Review Notes For Permit 15080695
Permit Number 15080695
Review Stop B
Sequence Number 2
Notes
Date Text
2015-09-25 11:58:202ND REVIEW: FBC 2014 5TH ED.
  
 THE RE-SUBMITTED TEST ARE FOR A CONDITION THAT MAY NOT
 EXIST IN THE PROPOSED LOCATION. SHOW THAT THE EXISTING
 CONDITION IS THE SAME AS DESCRIBED IN THE SOUND TESTS,
 OR PROVIDE A PRODUCT WITH TESTING CONDITIONS EQUIVALENT
 TO THE PROPOSED INSTALLATION.
  
 PLEASE SUBMIT PRODUCT TEST REPORTS TO DEMONSTRATE
 COMPLIANCE WITH THE FOLLOWING:
  
 FBC 603.1 FLAME SPREAD
  
 FBC 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 FOR YOU CONVENIENCE, YOU MAY E-MAIL REPORTS TO ME.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  