Plan Review Notes
Plan Review Notes For Permit 15080680
Permit Number 15080680
Review Stop P
Sequence Number 2
Notes
Date Text
2016-03-27 05:02:151) THE RESPONSE TO PLUMBING PLAN REVIEW COMMENT #5 FROM
 THE 8/31/15 REVIEW IS VAGUE. THE RESPONSE FROM EMERALD
 ENGINEERING REGARDING THE DISPOSAL OF THE GREASE WASTE
 FROM THE GRILL & GRIDDLE ON THE 3RD FLOOR LACKS
 SPECIFICS. EXPLAIN HOW THIS WASTE WILL BE ENTERED INTO
 THE GREASE INTERCEPTOR.WHAT PROCEDURES WILL BE IN PLACE
 TO ENSURE THIS WASTE IS DISCHARGED INTO THE GREASE
 INTERCEPTOR AND HOW?
 2) CLARIFY THE GREASE INTERCEPTOR SIZING ON SHT.P2.1 -
 THE PLANS NOTE "3 COMP.SINK POT SINK EACH COMPT. 20 X16
 X12 " AND THEN IT ALSO STATES THAT EACH COMPARTMENT IS
 20 X 16 X 9. WHICH IS IT? FBC 107.1.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR