Plan Review Notes For Permit 15080680 |
Permit Number |
15080680 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-03-27 05:02:15 | 1) THE RESPONSE TO PLUMBING PLAN REVIEW COMMENT #5 FROM | | THE 8/31/15 REVIEW IS VAGUE. THE RESPONSE FROM EMERALD | | ENGINEERING REGARDING THE DISPOSAL OF THE GREASE WASTE | | FROM THE GRILL & GRIDDLE ON THE 3RD FLOOR LACKS | | SPECIFICS. EXPLAIN HOW THIS WASTE WILL BE ENTERED INTO | | THE GREASE INTERCEPTOR.WHAT PROCEDURES WILL BE IN PLACE | | TO ENSURE THIS WASTE IS DISCHARGED INTO THE GREASE | | INTERCEPTOR AND HOW? | | 2) CLARIFY THE GREASE INTERCEPTOR SIZING ON SHT.P2.1 - | | THE PLANS NOTE "3 COMP.SINK POT SINK EACH COMPT. 20 X16 | | X12 " AND THEN IT ALSO STATES THAT EACH COMPARTMENT IS | | 20 X 16 X 9. WHICH IS IT? FBC 107.1.1. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | |
|