2015-09-04 09:36:231ST REVIEW: FBC 2014 MECHANICAL
 REVISION TRACKING #15080680
 MASTER #13060638
  
 1) THE SUBMITTED REVISION NARRATIVE FROM ROBERT IBARRA
 ARCHITECT DOES NOT LIST AND CLARIFY MANY OF THE
 MECHANICAL CHANGES THAT ARE SHOWN ON THE REVISED PLANS.
 PLEASE INCLUDE THE FOLLOWING PLAN REVISIONS IN THE
 NARRATIVE AND CLARIFY WHY THE CHANGES WERE MADE.
 SHEET M0.1- A) A NEW SUPPLY REGISTER HAS BEEN ADDED
 (AD-6) TO THE AIR DISTRIBUTION SCHEDULE. B) AHU-4 HAS A
 REVISION CLOUD AROUND IT IN THE SCHEDULE, BUT IT IS THE
 SAME UNIT THAT WAS SHOWN IN THE MASTER PLANS. C) THE
 F-2 HAS BEEN CHANGED TO A LARGER SIZE CAPACITY AND
 MODEL.
 M1.1 & M1.2: THE AD-2 SUPPLY DIFFUSERS HAVE BEEN
 CHANGED TO A DIFFERENT MODEL AND TYPE- THE AIR
 DISTRUBUTION SCHEDULE ON M0.1 DOES NOT SHOW THIS
 CHANGE.
 M1.2: THE PREP 2 ROOM HAS BEEN REDUCED IN WIDTH-
 CLARIFY WHY THE ROOM SIZE WAS CHANGED, WHAT EQUIPMENT
 WAS REMOVED OR RELOCATED, AND WHAT AIR DISTRIBUTION
 (DUCTWORK) ALTERATIONS HAVE BEEN MADE.
 M1.3: THE RESTROOMS HAVE ENLARGED IN SIZE AND AN
 ELECTRICAL ROOM HAS BEEN EITHER REMOVED OR BEEN
 RELOCATED- ALONG WITH OTHER FLOOR PLAN CHANGES.
 ADDITIONALLY THE RTU-1 HAS BEEN RELOCATED AND
 ALTERATIONS TO THE AIR DISTRIBUTION SYSTEM HAVE BEEN
 MADE.
 M1.4: A NEW EQUIPMENT PLATFORM FOR SUPPORT OF THE AC
 CONDENSERS IS SHOWN ON THE PLAN WITH A NOTE REFERENCING
 THE ARCHITECTURAL DRAWINGS. REVIEW OF THE
 ARCHITECTRURAL DRAWINGS INDICATES THAT FURTHER DETAILS
 ARE REQUIRED. PLEASE PROVIDE: A) SHOP DRAWINGS WITH
 REVIEW AND APPROVAL STAMPS BY THE ENGINEER OF RECORD.
 B) REVISED STRUCTURAL DRAWINGS INCLUDING DESIGN
 CRITERIA AND CALCULATIONS, ASSEMBLY AND ATTACHMENT
 DETAILS, TIE DOWN ENGINEERING FOR MOUNTING THE
 CONDENSERS TO THE PLATFORM, A PERMANENT MEANS OF ACCESS
 FOR SERVICE OF THE EQUIPMENT, AND DRAWINGS AND DETAILS
 FOR GUARDS (REFER TO SECTION 304.11 FBC-10 MECHANICAL).
 M1.5: INDICATE THE TYPE AND THICKNESS OF REFRIGERANT
 PIPING INSULATION AND HOW THE INSULATION AND PIPING
 WILL BE PROTECTED FROM WEATHERING AND UV DEGRADATION.
 2) PLEASE NOTE THAT REVISIONS TO THE KITCHEN HOOD
 SYSTEMS, AND THE WALK-IN COOLER AND FREEZER BOXES ARE
 TO BE SUBMITTED UNDER A SEPARATE PERMIT AS REQUIRED BY
 THE CITY OF WPB BUILDING DEPARTMENT. REVIEWS ON THOSE
 PLAN REVISIONS ARE ON HOLD UNTIL THOSE APPLICATIONS AND
 PLAN REVISIONS HAVE BEEN RECEIVED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER