2015-10-09 13:54:25114 SOUTH OLIVE AVENUE
 TRACKING #15080680
 PERMIT #13060638
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A1.3: OCCUPANTS SHALL NOT BE REQUIRED TO EGRESS
 THROUGH A STORAGE OCCUPANCY (DRY STORAGE #308).
  
 SHEET P2.3: THERE APPEARS TO BE STORM DRAIN PIPING
 ROUTED THROUGH STAIR #1.
  
 NO SHEET E2.3 SUBMITTED SHOWING THE ELECTRICAL CHANGES
 TO THE THIRD FLOOR.
  
 A SITE VISIT TO THE THIRD FLOOR OF THE REVEALED THAT
 THERE IS AN EXISTING BUILDING WITH WINDOW EXPOSURES
 ABUTTING THE ROOFTOP SEATING AND STAIR #1. HOW WILL
 THIS BE PROTECTED FROM FIRE?
  