2015-11-04 12:02:08 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION |
| OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 2010 |
| EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS |
| APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED. |
| 1. ALL FIRE ALARM WORK SHALL BE UNDER A SEPARATE PERMIT |
| W/SEPARATE SUBMITTAL DOCUMENTS. |
| 2. NEC 210.8(B): ALL 15 -20 AMP 125 VOLT OUTLETS IN |
| KITCHEN AND PREP AREAS SHALL BE ON GFI CIRCUIT. THIS |
| APPLIES TO ALL LEVELS THROUGHOUT THE PREMISES. |
| 3. NEC 210.62: THERE SHALL BE A SHOW WINDOW OUTLET FOR |
| EVERY 12? OF SHOW WINDOW OR MAJOR PORTION THEREOF. |
| 4. ALL LIGHTING SHALL COMPLY WITH THE MANDATORY |
| REQUIREMENTS OF 2010 FBC-ENERGY CONSERVATION SECTION |
| 505. |
| 5. YOU SHALL PROVIDE A FIXTURE SCHEDULE IDENTIFYING |
| FIXTURE. INDICATE WHICH OF THOSE HAS A BACKUP BATTERY |
| FOR EMERGENCY OPERATIONS OF EGRESS LIGHTING. |
| 6. YOU SHALL SUBMIT A 3RD FLOOR LIGHTING PLAN. |
| 7. EXIT LIGHTS SHALL BE AS INDICATED IN 2010 FBC |
| SECTION 1006.3. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| |