2015-11-04 12:02:08THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 2010
 EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS
 APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED.
 1. ALL FIRE ALARM WORK SHALL BE UNDER A SEPARATE PERMIT
 W/SEPARATE SUBMITTAL DOCUMENTS.
 2. NEC 210.8(B): ALL 15 -20 AMP 125 VOLT OUTLETS IN
 KITCHEN AND PREP AREAS SHALL BE ON GFI CIRCUIT. THIS
 APPLIES TO ALL LEVELS THROUGHOUT THE PREMISES.
 3. NEC 210.62: THERE SHALL BE A SHOW WINDOW OUTLET FOR
 EVERY 12? OF SHOW WINDOW OR MAJOR PORTION THEREOF.
 4. ALL LIGHTING SHALL COMPLY WITH THE MANDATORY
 REQUIREMENTS OF 2010 FBC-ENERGY CONSERVATION SECTION
 505.
 5. YOU SHALL PROVIDE A FIXTURE SCHEDULE IDENTIFYING
 FIXTURE. INDICATE WHICH OF THOSE HAS A BACKUP BATTERY
 FOR EMERGENCY OPERATIONS OF EGRESS LIGHTING.
 6. YOU SHALL SUBMIT A 3RD FLOOR LIGHTING PLAN.
 7. EXIT LIGHTS SHALL BE AS INDICATED IN 2010 FBC
 SECTION 1006.3.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  