2015-10-07 08:36:05 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 15080680 |
| W. P. B. PERMIT: 13060638 |
| ADD: 114 S. OLIVE AVE. |
| CONT: DWYOR CONSTRUCTION & DEVELOPMENT |
| TEL: (561)856-6655 |
| E-MAIL: ????????????????????? |
| |
| 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. OCT. 07/2015 |
| ACTION: DENIED |
| |
| 1) SHEET A1.1. THE FRONT ENTRY INDICATES THAT THERE IS |
| NO A SLOPED PORTION OF THE FLOOR LESS THAN OR EQUAL TO |
| 1:20. THE PLANS DO NOT PROVIDE WHAT THE ELEVATION |
| CHANGE FROM THE STREET TO THE FLAT FINISH FLOOR AND AT |
| WHAT DISTANCE THIS SLOPED AREA OF THE FLOOR IS TO |
| DETERMINE IF THIS IS A RAMP OR JUST A SLOPED SURFACE OF |
| THE FLOOR. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED |
| TO DETERMINE CODE COMPLIANCE WITH EITHER GRADE OR RAMP. |
| 2010 FBC-ACCESSIBLITY DEFITIONS 106 RAMP : RUNNING |
| SLOPE STEEPER THAN 1:20. |
| |
| 2) SHEET A1.1. NEW FIRE SPRINKLER ROOM 106 DOES NOT |
| INDICATE WALL TAGS IDENTIFYING THE TYPE OF WALL |
| CONSTRUCTION FOR THIS SPACE. 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED FOR CODE COMPLIANCE. |
| |
| 3) SHEET A1.1 THE SECOND FLOOR PLAN WITH THE NEW FLOOR |
| PLAN AND SEATING ARRANGEMENT AND COLUMN LAYOUT PLEASE |
| SHOW COMPLIANCE WITH 2010 FBC-B 1014.3 EXCEPTION #5. |
| WHERE A TENANT SPACE IN A GROUP A OCCUPANCY HAS AN |
| OCCUPANT LOAD OF MORETHAN 50, THE LENGTH OF A COMMON |
| PATH OF TRAVEL SHALL NOT BE MORE THAN 20 FT. NOTE ALSO |
| PROVIDE THE ACCESS AISLES SHOWING COMPLIANCE WITH |
| 1017.4.3 AISLES ACCESSWAYS SHALL NOT EXCEED 30 FT FROM |
| ANY SEAT TO THE POINT WHERE A PERSON HAS 2 OR MORE |
| PATHS OF EGRESS TRAVEL TO SEPARATE EXITS. |
| |
| 4) SHEET A1.1 THE 3RD FLOOR PLAN THE NORTH EAST CORNER |
| OF THE SEATING AREA SHOW COMPLIANCE WITH 1017.4.3 |
| AISLES ACCESSWAYS SHALL NOT EXCEED 30 FT FROM ANY SEAT |
| TO THE POINT WHERE A PERSON HAS 2 OR MORE PATHS OF |
| EGRESS TRAVEL TO SEPARATE EXITS. |
| |
| 5) SHEET A1.2. ROOM 209 THE ELEVAOR EQUIPMENT ROOM DOES |
| NOT HAVE WALL TAGS IDENTIFYING THE TYPE OF WALL |
| CONSTRUCTION IN ACCORDANCE WITH 2010 FBC-B 3006.4 |
| MACHINE ROOMS 1 HOUR FIRE BARRIER. |
| |
| 6) SHEET A1.2 ROOM # 208 THE UNISEX RESTROOM DOOR # |
| 208.01 THE WAY THIS DOOR SWINGS REQUIRES 42 INCHES OF |
| WALL ON THE LATCH SIDE OF THE DOOR. PLEASE REVIEW 2010 |
| ACCESSIBILITY CODE FIGURE 404.2.4.1 (E). |
| |
| 7) SHEET A1.3, DOOR 304.01 DOES NOT HAVE THE REQUIRED |
| 18 INCHES CLEAR WIDTH ON THE LATCH SIDE OF THE DOOR. |
| 2010 FBC-ACCESSIBLITY CODE. 404.2.4 MAEUVERING |
| CLEARENCES, AND FIGURE 404.2.4.1( A) . |
| |
| 8) SHEET A1.1 THE 3RD FLOOR. THE STANDING ROOM ONLY |
| NEXT TO THE PROPERTY LINE WALL. SHEET A5.2 NOTE CON A. |
| CONCRETE BLOCK RAILING TO 48 INCHES AFF. PLEASE NOTE |
| THIS IS A REVISION FROM WHAT IS SHOWN ON A7.1.1 |
| SECTIONS 02 & 03. THE DETAILS 02 & 03 SHOW A BLOCK WALL |
| 2 FOOT 3 INCHES ABOVE THE 3RD FLOOR WITH A GLASS |
| RAILING TO THE HEIGTH OF 3 FOOT 8 INCHES. PLEASE UPDATE |
| SHEET A7.1.1. |
| |
| NOTE THE 3 FOOT 8 INCHES BLOCK WALL/ GUARDRAIL IS MORE |
| RESTRICTIVE THAN THE REQUIRED 42 INCHES, SHEET A1.1 THE |
| 3RD FLOOR PLAN SHOWS THE SOFA SEATING 4 FOOT 6 INCHES |
| AWAY FROM THE BLOCK WALL/ GUARD RAIL, THERE IS NO |
| ADJACENT FIXED SEATING FBC-B 1013.2) TO BE COMPLIED |
| WITH!!!!!!! |
| |
| 9A) SHEET A5.1 THE SOUTH ELEVATION DOES NOT SHOW |
| WINDOWS ON THE 3RD OR 4 THE FLOORS IN THE ADJACENT |
| BUILDING, JUST A BLANK WALL. INSPECTORS ON THE JOBSITE |
| HAVE VERIFIED THERE ARE WINDOWS IN THESE WALLS. PLEASE |
| SHOW HOW COMPLIANCE WITH STEPPED BUILDING 2010 FBC-B |
| 706.6.1. WHERE A FIRE WALL SERVES AS AN EXTERIOR WALL |
| FOR A BUILDING AND SEPARATES BUILDINGS HAVING DIFFERENT |
| ROOF LEVELS, SUCH WALL SHALL TERMINATE AT A POINT NOT |
| LESS THAN 30 INCHES (762 MM) ABOVE THE LOWER ROOF |
| LEVEL, PROVIDED THE EXTERIOR WALL FOR A HEIGHT OF 15 |
| FEET (4572 MM) ABOVE THE LOWER ROOF IS NOT LESS THAN |
| 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION FROM BOTH |
| SIDES WITH OPENINGS PROTECTED BY FIRE ASSEMBLIES HAVING |
| A FIRE PROTECTION RATING OF NOT LESS THAN 3/4 HOUR. |
| EXCEPTION: WHERE THE FIRE WALL TERMINATES AT THE |
| UNDERSIDE OF THE ROOF SHEATHING, DECK OR SLAB OF THE |
| LOWER ROOF, PROVIDED: 1. THE LOWER ROOF ASSEMBLY WITHIN |
| 10 FEET (3048 MM) OF THE WALL HAS NOT LESS THAN A |
| 1-HOUR FIRE-RESISTANCE RATING AND THE ENTIRE LENGTH AND |
| SPAN OF SUPPORTING ELEMENTS FOR THE RATED ROOF ASSEMBLY |
| HAS A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR. |
| 2. OPENINGS IN THE LOWER ROOF SHALL NOT BE LOCATED |
| WITHIN 10 FEET (3048 MM) OF THE FIRE WALL. |
| |
| 9B) 2010 FBC-B 706.8 OPENINGS. EACH OPENING THROUGH A |
| FIRE WALL SHALL BE PROTECTED IN ACCORDANCE WITH SECTION |
| 716.5 AND SHALL NOT EXCEED 156 SQUARE FEET (15 M2). THE |
| AGGREGATE WIDTH OF OPENINGS AT ANY FLOOR LEVEL SHALL |
| NOT EXCEED 25 PERCENT OF THE LENGTH OF THE WALL. |
| EXCEPTIONS: |
| 1. OPENINGS ARE NOT PERMITTED IN PARTY WALLS |
| CONSTRUCTED IN ACCORDANCE WITH SECTION 706.1.1. |
| 2. OPENINGS SHALL NOT BE LIMITED TO 156 SQUARE FEET (15 |
| M2) WHERE BOTH BUILDINGS ARE EQUIPPED THROUGHOUT WITH |
| AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE |
| WITH SECTION 903.3.1.1. |
| |
| 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |