2015-11-10 16:02:32 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, |
| FAC9N-3, FBC 5TH EDITION RESIDENTIAL 301. |
| |
| 2ND REVIEW, PROVIDE THE PRODUCT APPROVAL FOR THE PAN |
| ROOF. |
| 3RD REVIEW, NOT ADDRESSED. THE PRODUCT APPROVAL IS |
| AVAILABLE AT WWW.FLORIDABUILDING.ORG. |
| |
| 2. SEE FBC 5TH ED. RESIDENTIAL TABLE 302.1(1), SHOW |
| DISTANCE FROM PROPOSED PAN ROOF TO PROPERTY LINE. IF |
| ANY PART OF THE PAN ROOF IS WITHIN 5' OF THE PROPERTY |
| LINE, A 1 HOUR FIRE RESISTANCE RATING IS REQUIRED. |
| |
| 2ND REVIEW, PLAN WAS REVISED TO STATE TO ADJUST TO |
| SETBACK. SITE PLAN WAS NOT REVISED. REVISE THE SITE |
| PLAN TO CLEARLY SHOW THE WIDTH OF THE PROPOSED ROOF AND |
| THE DISTANCE TO THE PROPERTY LINE. |
| 3RD REVIEW, ONLY ONE SET OF THE REVISED SITE PLAN |
| PROVIDED. SEE OTHER COMMENTS REGARDING PLAN SUBMISSION. |
| |
| 3. WHEN RESUBMITTING, PROVIDE TWO COMPLETE COLLATED |
| SETS OF PLANS FOR PERMIT ISSUANCE. OLD SHEETS SHOULD BE |
| RETAINED IN THE PACKAGE BUT MARKED "VOID". |
| |
| 3RD REVIEW, NOT ADDRESSED. THERE SHOULD BE TWO COMPLETE |
| COLLATED SETS OF PLANS FOR PERMIT ISSUANCE, OLD SETS |
| MARKED "VOID." AN ATTEMPT WAS MADE TO REDLINE THIS |
| PLAN, BUT THERE ARE NOT TWO COMPLETE SETS AND THE |
| PRODUCT APPROVAL WAS NOT PROVIDED. THE COLLATED SETS |
| SHOULD BE IDENTICAL AND SHOULD NOT INCLUDE DUPLICATE |
| PAGES. SOME SHEETS ARE STAPLED ON TWO SIDES SO THE |
| PACKAGE CANNOT OPEN, OTHER SHEETS ARE UPSIDE DOWN. ONE |
| SET HAS TWO SITE SPECIFIC PLANS WHICH ARE IDENTICAL. A |
| LOOSE PAGE HAS HAND DRAWN CHANGES ON IT; IT IS NOT |
| CLEAR WHY THIS WAS SUBMITTED. |
| |
| NEW COMMENTS: |
| |
| 4. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS |
| FS471. |
| |
| 5. BASED ON THE PLANS PROVIDED, THE 3' DOOR ENCROACHES |
| THE PROPERTY LINE (2' SETBACK). ALL WORK FOR THIS |
| PERMIT IS TO BE CONTAINED IN THE PARCEL. WORK ON OTHER |
| PARCELS REQUIRE A SEPARATE PERMIT APPLICATION, FBC 107. |
| ALSO, THE SITE PLAN SHOWS A 4' GATE; NOT CLEAR WHAT |
| THIS IS. |
| |
| |