Plan Review Notes
Plan Review Notes For Permit 15080661
Permit Number 15080661
Review Stop E
Sequence Number 4
Notes
Date Text
2016-04-05 17:47:42ELECTRICAL REVIEW COMMENTS
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011
 EDITION
  
 CORRECTIONS REQUIRED:
 1. THE RISER DIAGRAM SHOWS THE SERVICE AS 277/480 3
 PHASE GOING INTO A STEP DOWN TRANSFORMER TO 120/208 BUT
 THE SERVICE REQUIREMENT AS PER THE PANEL SCHEDULE IS
 120/240 3 PHASE GOING INTO A 3 PHASE DISC. OF WHICH TWO
 PHASES ARE BEING USED.
 2. THE PANEL SCHEDULE ON THE PRIMARY PERMIT HAS A
 DEMAND LOAD OF 54.8 AMP AND THE PANEL SCHEDULE ON THE
 NEW PLANS HAVE A CONNECTED DEMAND LOAD OF 73.6 AMP.
 SUBMIT SPECS
 3. THE RISER DOES NOT INDICATE THE CONDUCTOR INSULATION
 RATING THEREFORE ASSUMING IT IS 60 DEGREE, THE MAXIMUM
 DISTANCE BETWEEN THE MAIN DISC AND THE TRAILERS DISC IS
 ONLY 136'.
 4. PHYSICAL PROTECTION AS REQUIRED IN NEC 110.27(B)
 SHALL BE PROVIDED AND INDICATED ON PLANS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  