2015-10-28 09:33:06 | ****CORRECTIONS**** |
| |
| A DCA APPROVED MANUFACTURED BUILDING IS PROPOSED, WITH |
| MODIFICATIONS - PERMIT WILL BE ISSUED WITH PROVISO |
| THAT, UPON BUILDING INSPECTION, THE DCA/DBPR INSIGNIA |
| WILL BE REMOVED AND RETURNED TO DBPR. |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1 OK |
| 2 OK |
| |
| 3. A DOOR IS TO BE REMOVED AND WALL INFILL INSTALLED. |
| PROVIDE A STRUCTURAL DETAIL AND INCLUDE WIND DESIGN |
| CRITERIA FBC 1603.1.4. |
| |
| 4. OK |
| |
| 5. DETAIL 3 SK5, SEAT HEIGHT NOT CLEAR, FBC 5TH ED |
| ACCESSIBILITY 604.4, PLEASE REVISE TO CLARIFY. DETAIL 2 |
| SK5, PROVIDE LAV HEIGHT AND KNEE CLEARANCE, 606.3. |
| 2ND REVIEW, DISTANCE TO TOP OF LID (NOT SEAT) IS SHOWN |
| AS BOTH 1FT4IN AND 1FT5IN WHICH WOULD BE 16 AND 17 |
| INCHES, SO SEAT WOULD BE LOWER, BUT SEAT IS REQUIRED TO |
| BE BETWEEN 17 AND 19 INCHES. THIS CAN BE A REDLINED |
| ITEM UPON REQUEST. |
| |
| 5. THE PLANS FOR STAIRS, RAMP, LANDING, RAILING ARE |
| DEFICIENT. IT REFERS TO THE WRONG CODE, AN OLD VERSION |
| OF ASCE7, AND IS LACKING THE DIMENSIONS WHICH SHOULD |
| SHOW COMPLIANCE. REVISE PLANS TO SHOW COMPLIANCE WITH |
| ALL REQUIREMENTS OF FBC 5TH EDITION ACCESSIBILITY |
| (DIMENSIONS). DETAILS NOT NEEDED FOR THIS JOB CAN BE |
| CROSSED OUT AND DO NOT NEED TO DEMONSTRATE COMPLIANCE. |
| |
| 6. SHEET SP1 SHOWS 38.8 FT FROM PROPOSED SALES OFFICE |
| TO EXISTING RESNICK BUILDING. REVISE TO SHOW ASSUMED |
| PROPERTY LINE BETWEEN THE TWO BUILDINGS, FBC 705.3 AND |
| SHOW COMPLIANCE WITH FBC TABLES 602, 705.8. |
| |
| 2ND REVIEW, PAGE WAS REVISED TO SHOW A DISTANCE OF 28.8 |
| BUT THE ASSUMED PROPERTY LINE, DISTANCE FROM EACH |
| BUILDING TO THE ASSUMED PROPERTY LINE, COMPLIANCE WITH |
| TABLES 602, 705.8 NOT SHOWN. PLEASE CONTACT ME IF YOU |
| WISH TO DISCUSS. |
| |
| 7. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED, |
| OR PROVIDE REMOVAL AGREEMENT REQUESTED BY WILLIE SWOPE, |
| 561 233 5025. |
| |
| 8. IMPACT PROTECTION REQUIRED, SEE SITE INSTALLED |
| ITEMS, FBC 1609.1.4. IF SHUTTERS ARE PROPOSED, PROVIDE |
| THE PRODUCT APPROVAL AND COMPLETE THE SAMPLE |
| INSTALLATION SCHEDULE: |
| |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/SCHEDULE_FOR_INSTALLATION.PDF |
| |
| THIS CAN BE A PROVISO ITEM, SEPARATE PERMIT REQUIRED. A |
| PRODUCT APPROVAL WAS PROVIDED BUT THE FORM WAS NOT |
| INCLUDED. |
| |
| 9. SHEET A4 IS NOT A PART OF THE MODULAR STATE |
| APPROVAL. REVISE TO UPDATE TO CURRENT CODE, REVISE |
| PLANS TO COMPLY WITH CURRENT CODE, AND ALSO SEE FBC |
| 1809.4 REGARDING FOOTING DEPTH. |
| |
| |
| WHEN RESUBMITTING, PLEASE REMOVE THE OLD SHEETS FROM |
| THE COLLATED PERMIT DOCUMENTS BUT RETAIN IN THE |
| SUBMITTAL FOR REFERENCE. PLEASE RETAIN THE VOIDED |
| REFERENCE ONLY 2010 MODULAR PLANS. PLEASE SEE ME OR |
| STEVE KENNEDY IF YOU NEED ASSISTANCE. |
| |